Table 8.12.A. U.S. Transmission Circuit Sustained Automatic Outage Counts and Hours
by High-Voltage Size and NERC Region, 2011
 

Sustained Automatic Outage Counts
Voltage Region
Type Operating (kV) FRCC MRO NPCC RFC SERC SPP TRE WECC Contiguous U.S.
AC 200-299 116 65 12 153 276 58 -- 488 1,168
AC 300-399 -- 64 73 105 69 60 132 228 731
AC 400-599 5 5 -- 16 117 1 -- 123 267
AC 600+ -- -- 2 12 -- -- -- -- 14
AC Total   121 134 87 286 462 119 132 839 2,180
DC 100-199 -- -- -- -- -- -- -- -- --
DC 200-299 -- 20 -- -- -- -- -- 2 22
DC 300-399 -- -- -- -- -- -- -- -- --
DC 400-499 -- 7 -- -- -- -- -- -- 7
DC 500-599 -- -- -- 6 -- -- -- 9 15
DC 600+ -- -- -- -- -- -- -- -- --
DC Total   -- 27 -- 6 -- -- -- 11 44
Grand Total   121 161 87 292 462 119 132 850 2,224

 

Total Outages per 1,000 Circuit Miles
  Region
  FRCC MRO NPCC RFC SERC SPP TRE WECC Contiguous U.S.
Rate   16.99 7.67 12.75 11.49 13.89 15.34 13.89 13.71 12.87

 

Sustained Automatic Outage Hours
Voltage Region
Type Operating (kV) FRCC MRO NPCC RFC SERC SPP TRE WECC Contiguous U.S.
AC 200-299 1,651 7,043 91 9,220 11,860 421 -- 6,686 36,972
AC 300-399 -- 3,206 10,484 5,626 2,774 685 1,909 1,114 25,797
AC 400-599 24 11 -- 11,874 14,909 * -- 1,071 27,889
AC 600+ -- -- 4 185 -- -- -- -- 189
AC Total   1,675 10,260 10,579 26,906 29,543 1,106 1,909 8,870 90,847
DC 100-199 -- -- -- -- -- -- -- -- --
DC 200-299 -- 252 -- -- -- -- -- 6 258
DC 300-399 -- -- -- -- -- -- -- -- --
DC 400-499 -- 272 -- -- -- -- -- -- 272
DC 500-599 -- -- -- 358 -- -- -- 299 657
DC 600+ -- -- -- -- -- -- -- -- --
DC Total   -- 524 -- 358 -- -- -- 305 1,187
Grand Total   1,675 10,784 10,579 27,264 29,543 1,106 1,909 9,175 92,034

 

Outage Hours per Outage Incident
  Region
  FRCC MRO NPCC RFC SERC SPP TRE WECC Contiguous U.S.
Rate   13.84 66.98 121.59 93.37 63.95 9.29 14.46 10.79 41.38

Notes:
* = Value is less than half of the smallest unit of measure. (e.g., for values with no decimals, the smallest unit is 1 then values under 0.5 are shown as *.)
Circuit Miles for each region is displayed in Table 8.10.A.
An Automatic Outage is an outage which results from the automatic operation of a switching device, causing an Element to change from an In-Service State to a not In-Service State.
A Sustained Outage is an automatic outage with an outage duration of a minute or greater.
Source: U.S. Energy Information Administration, Form EIA-411, "Coordinated Bulk Power Supply Program Report."