| Released: September, 2008 | ||||||||||||||||||||||
| Table E6A. Electricity Consumption (kWh) Intensities by End Use
for All Buildings, 2003 |
||||||||||||||||||||||
| Electricity Energy Intensity (kWh/square foot) | ||||||||||||||||||||||
| Total | Space Heat- ing |
Cool- ing |
Venti- lation |
Water Heat- ing |
Light- ing |
Cook- ing |
Refrig- eration |
Office Equip- ment |
Com- puters |
Other | ||||||||||||
| All Buildings ......................... | 14.9 | 0.7 | 2.0 | 1.8 | 0.4 | 5.6 | 0.1 | 1.6 | 0.3 | 0.7 | 1.7 | |||||||||||
| Building Floorspace | ||||||||||||||||||||||
| (Square Feet) | ||||||||||||||||||||||
| 1,001 to 5,000 ......................... | 17.8 | 0.9 | 2.0 | 0.8 | 0.5 | 4.4 | 0.3 | 6.2 | 0.4 | 0.5 | 1.8 | |||||||||||
| 5,001 to 10,000 ....................... | 12.9 | 0.8 | 1.7 | 0.8 | 0.3 | 4.2 | 0.2 | 2.5 | 0.3 | 0.4 | 1.7 | |||||||||||
| 10,001 to 25,000 ..................... | 11.4 | 0.6 | 1.3 | 1.2 | 0.3 | 4.3 | 0.1 | 1.3 | 0.2 | 0.5 | 1.5 | |||||||||||
| 25,001 to 50,000 ..................... | 12.8 | 0.6 | 2.0 | 1.8 | 0.4 | 4.5 | 0.1 | 1.2 | 0.2 | 0.6 | 1.5 | |||||||||||
| 50,001 to 100,000 ................... | 14.9 | 0.8 | 2.2 | 2.2 | 0.4 | 5.8 | 0.1 | 1.0 | 0.2 | 0.6 | 1.7 | |||||||||||
| 100,001 to 200,000 ................. | 16.9 | 0.7 | 2.4 | 2.6 | 0.3 | 6.7 | (*) | 0.9 | 0.4 | 0.9 | 2.0 | |||||||||||
| 200,001 to 500,000 ................. | 15.2 | 0.4 | 2.2 | 2.2 | 0.2 | 6.8 | 0.1 | 0.4 | 0.3 | 0.8 | 1.8 | |||||||||||
| Over 500,000 .......................... | 19.2 | 0.9 | 2.6 | 2.6 | 0.4 | 8.4 | 0.1 | 0.7 | 0.3 | 0.9 | 2.1 | |||||||||||
| Principal Building Activity | ||||||||||||||||||||||
| Education ................................ | 11.0 | 0.5 | 2.2 | 2.5 | 0.3 | 3.4 | (*) | 0.5 | 0.1 | 1.0 | 0.6 | |||||||||||
| Food Sales .............................. | 49.4 | 1.5 | 2.9 | 1.8 | Q | 10.9 | 0.6 | 28.2 | 0.5 | 0.4 | 2.4 | |||||||||||
| Food Service .......................... | 38.4 | 1.8 | 5.0 | 4.3 | 1.8 | 7.5 | 2.4 | 12.3 | 0.3 | 0.3 | 2.6 | |||||||||||
| Health Care ............................. | 22.9 | 0.5 | 3.1 | 3.9 | 0.2 | 9.7 | 0.1 | 0.8 | 0.3 | 0.9 | 3.3 | |||||||||||
| Inpatient ................................ | 27.5 | 0.5 | 3.8 | 5.9 | 0.3 | 11.7 | 0.1 | 0.6 | 0.3 | 1.0 | 3.2 | |||||||||||
| Outpatient ............................. | 16.1 | 0.7 | 2.1 | 1.0 | 0.1 | 6.6 | (*) | 1.0 | 0.4 | 0.8 | 3.5 | |||||||||||
| Lodging ................................... | 13.5 | 0.8 | 1.4 | 0.8 | 0.7 | 7.1 | 0.1 | 0.7 | Q | 0.4 | 1.4 | |||||||||||
| Mercantile ............................... | 19.2 | 1.5 | 2.9 | 1.8 | 1.0 | 8.1 | 0.1 | 1.3 | 0.2 | 0.3 | 2.2 | |||||||||||
| Retail (Other Than Mall) ........ | 14.3 | 0.4 | 1.7 | 1.1 | 0.1 | 7.5 | (*) | 1.5 | 0.2 | 0.3 | 1.5 | |||||||||||
| Enclosed and Strip Malls ....... | 22.3 | 2.2 | 3.6 | 2.2 | 1.5 | 8.4 | 0.1 | 1.2 | 0.2 | 0.3 | 2.6 | |||||||||||
| Office ...................................... | 17.3 | 0.8 | 2.4 | 1.5 | 0.2 | 6.8 | (*) | 0.8 | 0.8 | 1.8 | 2.2 | |||||||||||
| Public Assembly ..................... | 12.5 | 0.4 | 2.6 | 4.7 | (*) | 2.0 | (*) | 0.7 | Q | 0.2 | 1.7 | |||||||||||
| Public Order and Safety ......... | 15.3 | 0.5 | 2.1 | 2.8 | 0.9 | 4.8 | (*) | 0.9 | 0.2 | 0.4 | 2.7 | |||||||||||
| Religious Worship ................... | 4.9 | 0.2 | 0.8 | 0.4 | (*) | 1.3 | (*) | 0.5 | (*) | 0.1 | 1.4 | |||||||||||
| Service ................................... | 11.0 | 0.4 | 1.1 | 1.8 | (*) | 4.6 | Q | 0.6 | 0.1 | 0.2 | 2.1 | |||||||||||
| Warehouse and Storage ........ | 7.6 | 0.2 | 0.4 | 0.6 | 0.1 | 4.1 | Q | 1.1 | 0.1 | 0.1 | 0.9 | |||||||||||
| Other ....................................... | 22.5 | 0.4 | 2.7 | 1.8 | 0.1 | 10.1 | Q | 1.8 | Q | 0.9 | 3.7 | |||||||||||
| Vacant .................................... | 2.4 | 0.1 | 0.2 | 0.2 | Q | 0.7 | Q | 0.1 | Q | (*) | 1.1 | |||||||||||
| Year Constructed | ||||||||||||||||||||||
| Before 1920 ............................ | 7.1 | 0.2 | 0.5 | 0.9 | Q | 2.7 | 0.1 | 1.3 | 0.2 | 0.3 | 0.9 | |||||||||||
| 1920 to 1945 ........................... | 9.4 | 0.2 | 0.7 | 1.3 | 0.1 | 4.0 | 0.1 | 1.1 | 0.1 | 0.4 | 1.3 | |||||||||||
| 1946 to 1959 ........................... | 10.2 | 0.4 | 1.2 | 1.5 | 0.2 | 3.9 | 0.1 | 1.1 | 0.2 | 0.5 | 1.2 | |||||||||||
| 1960 to 1969 ........................... | 12.3 | 0.5 | 1.6 | 1.8 | 0.3 | 4.3 | (*) | 1.4 | 0.2 | 0.6 | 1.5 | |||||||||||
| 1970 to 1979 ........................... | 16.7 | 1.0 | 2.2 | 2.1 | 0.4 | 6.4 | 0.1 | 1.6 | 0.3 | 0.7 | 2.0 | |||||||||||
| 1980 to 1989 ........................... | 18.8 | 1.0 | 2.8 | 2.0 | 0.6 | 7.1 | 0.1 | 1.8 | 0.4 | 0.9 | 2.2 | |||||||||||
| 1990 to 1999 ........................... | 17.6 | 0.8 | 2.6 | 2.2 | 0.5 | 6.3 | 0.1 | 2.0 | 0.4 | 0.8 | 2.0 | |||||||||||
| 2000 to 2003 ........................... | 16.9 | 0.8 | 2.6 | 1.8 | 0.4 | 6.6 | 0.1 | 2.0 | 0.2 | 0.5 | 1.9 | |||||||||||
| Census Region and Division | ||||||||||||||||||||||
| Northeast ................................ | 12.4 | 0.7 | 0.9 | 1.6 | 0.3 | 5.0 | 0.1 | 1.3 | 0.3 | 0.7 | 1.5 | |||||||||||
| New England ........................ | 12.0 | 0.8 | 0.7 | 1.3 | 0.4 | 4.7 | 0.1 | 1.8 | 0.2 | 0.6 | 1.4 | |||||||||||
| Middle Atlantic ....................... | 12.5 | 0.7 | 1.0 | 1.7 | 0.2 | 5.1 | (*) | 1.2 | 0.3 | 0.7 | 1.6 | |||||||||||
| Midwest .................................. | 13.2 | 0.9 | 0.9 | 1.8 | 0.2 | 5.2 | 0.1 | 1.5 | 0.3 | 0.6 | 1.7 | |||||||||||
| East North Central ................. | 13.8 | 0.8 | 0.9 | 2.0 | 0.2 | 5.5 | 0.1 | 1.5 | 0.3 | 0.7 | 1.8 | |||||||||||
| West North Central ............... | 12.0 | 1.1 | 1.0 | 1.4 | 0.3 | 4.4 | 0.1 | 1.6 | 0.2 | 0.5 | 1.5 | |||||||||||
| South ...................................... | 17.4 | 0.6 | 3.4 | 2.0 | 0.5 | 6.1 | 0.1 | 1.9 | 0.2 | 0.7 | 1.8 | |||||||||||
| South Atlantic ....................... | 18.3 | 0.7 | 3.3 | 2.1 | 0.6 | 6.6 | 0.2 | 2.0 | 0.3 | 0.8 | 1.9 | |||||||||||
| East South Central ................ | 16.2 | 0.7 | 2.2 | 2.0 | 0.4 | 6.0 | Q | 2.1 | 0.2 | 0.5 | 2.0 | |||||||||||
| West South Central ............... | 16.3 | 0.4 | 4.0 | 1.8 | 0.4 | 5.4 | 0.1 | 1.6 | 0.2 | 0.5 | 1.8 | |||||||||||
| West ....................................... | 14.7 | 0.7 | 1.9 | 1.7 | 0.3 | 5.7 | 0.1 | 1.4 | 0.5 | 0.7 | 1.8 | |||||||||||
| Mountain ............................... | 16.3 | 0.9 | 2.2 | 1.9 | 0.3 | 6.6 | 0.1 | 1.4 | Q | 0.6 | 1.9 | |||||||||||
| Pacific ................................... | 14.0 | 0.6 | 1.8 | 1.6 | 0.3 | 5.3 | 0.1 | 1.4 | 0.5 | 0.7 | 1.8 | |||||||||||
| Climate Zone: 30-Year Average | ||||||||||||||||||||||
| Under 2,000 CDD and -- | ||||||||||||||||||||||
| More than 7,000 HDD ............ | 12.1 | 0.9 | 0.7 | 1.7 | 0.2 | 4.7 | 0.1 | 1.6 | 0.2 | 0.5 | 1.5 | |||||||||||
| 5,500-7,000 HDD .................. | 13.7 | 0.9 | 1.0 | 1.7 | 0.3 | 5.6 | 0.1 | 1.5 | 0.3 | 0.6 | 1.7 | |||||||||||
| 4,000-5,499 HDD .................. | 15.3 | 0.8 | 1.6 | 1.8 | 0.3 | 6.1 | 0.1 | 1.5 | 0.5 | 0.8 | 1.8 | |||||||||||
| Fewer than 4,000 HDD ......... | 15.3 | 0.5 | 2.3 | 1.8 | 0.5 | 5.7 | 0.1 | 1.7 | 0.3 | 0.6 | 1.8 | |||||||||||
| 2,000 CDD or More and -- | ||||||||||||||||||||||
| Fewer than 4,000 HDD ......... | 18.5 | 0.3 | 5.1 | 2.0 | 0.6 | 5.9 | 0.1 | 1.6 | 0.2 | 0.8 | 1.9 | |||||||||||
| Number of Establishments | ||||||||||||||||||||||
| One ......................................... | 14.1 | 0.5 | 1.8 | 1.8 | 0.3 | 5.2 | 0.1 | 1.9 | 0.3 | 0.6 | 1.6 | |||||||||||
| 2 to 5 ....................................... | 14.4 | 0.6 | 1.9 | 1.7 | 0.3 | 5.7 | 0.1 | 1.3 | 0.3 | 0.6 | 1.8 | |||||||||||
| 6 to 10 ..................................... | 20.0 | 1.4 | 2.6 | 2.2 | 0.8 | 7.8 | (*) | 1.0 | 0.4 | 1.6 | 2.3 | |||||||||||
| 11 to 20 ................................... | 18.9 | 1.4 | 3.1 | 2.2 | 0.8 | 7.1 | (*) | 1.0 | 0.3 | 0.7 | 2.4 | |||||||||||
| More than 20 ........................... | 20.3 | 1.4 | 3.6 | 2.3 | 0.8 | 7.6 | 0.1 | 0.8 | 0.4 | 1.0 | 2.3 | |||||||||||
| Currently Unoccupied ............. | 1.8 | Q | Q | (*) | Q | 0.5 | Q | Q | Q | Q | 0.9 | |||||||||||
| Energy Sources (more than | ||||||||||||||||||||||
| one may apply) | ||||||||||||||||||||||
| Electricity ................................ | 14.9 | 0.7 | 2.0 | 1.8 | 0.4 | 5.6 | 0.1 | 1.6 | 0.3 | 0.7 | 1.7 | |||||||||||
| Natural Gas ............................. | 15.3 | 0.6 | 2.0 | 2.0 | 0.3 | 6.0 | 0.1 | 1.6 | 0.3 | 0.7 | 1.8 | |||||||||||
| Fuel Oil .................................... | 16.9 | 0.7 | 2.2 | 2.3 | 0.3 | 7.0 | 0.1 | 0.8 | 0.5 | 0.9 | 2.0 | |||||||||||
| District Heat ............................ | 18.1 | 0.3 | 1.3 | 3.7 | 0.2 | 7.9 | (*) | 0.7 | 0.2 | 1.5 | 2.3 | |||||||||||
| Energy End Uses (more than | ||||||||||||||||||||||
| one may apply) | ||||||||||||||||||||||
| Buildings with Space Heating . | 15.2 | 0.7 | 2.0 | 1.9 | 0.4 | 5.7 | 0.1 | 1.6 | 0.3 | 0.7 | 1.8 | |||||||||||
| Buildings with Cooling ............. | 15.9 | 0.8 | 2.2 | 1.9 | 0.4 | 5.9 | 0.1 | 1.7 | 0.3 | 0.7 | 1.8 | |||||||||||
| Buildings with Water Heating .. | 15.8 | 0.7 | 2.1 | 1.9 | 0.4 | 5.9 | 0.1 | 1.7 | 0.3 | 0.7 | 1.8 | |||||||||||
| Annual Consumption | ||||||||||||||||||||||
| (kilowatthours) | ||||||||||||||||||||||
| 10,000 or Less ....................... | 1.3 | (*) | 0.1 | 0.1 | (*) | 0.4 | (*) | 0.2 | (*) | (*) | 0.4 | |||||||||||
| 10,001 to 50,000 ..................... | 4.9 | 0.2 | 0.6 | 0.3 | 0.1 | 1.8 | (*) | 0.7 | 0.1 | 0.2 | 0.9 | |||||||||||
| 50,001 to 100,000 ................... | 8.1 | 0.4 | 1.0 | 0.6 | 0.2 | 2.6 | 0.1 | 1.6 | 0.2 | 0.3 | 1.2 | |||||||||||
| 100,001 to 500,000 ................. | 13.5 | 0.8 | 1.6 | 1.3 | 0.4 | 4.5 | 0.2 | 2.5 | 0.2 | 0.5 | 1.6 | |||||||||||
| 500,001 to 1,000,000 .............. | 15.0 | 0.7 | 2.3 | 1.9 | 0.5 | 5.3 | 0.1 | 1.8 | 0.2 | 0.5 | 1.5 | |||||||||||
| 1,000,001 to 5,000,000 ........... | 21.4 | 1.0 | 3.0 | 3.2 | 0.5 | 8.0 | 0.1 | 1.7 | 0.4 | 1.1 | 2.3 | |||||||||||
| Over 5,000,000 ....................... | 24.0 | 0.9 | 3.4 | 3.1 | 0.5 | 10.6 | 0.1 | 1.0 | 0.6 | 1.2 | 2.7 | |||||||||||
| See "Guide to the Tables" or "Glossary" for
further explanations of the terms used in this table. Both can be accessed
from the CBECS web site - http://www.eia.gov/consumption/commercial/. (*)=Value rounds to zero in the units displayed. Q=Data withheld because fewer than 20 buildings were sampled for any cell, or because the Relative Standard Error (RSE) was greater than 50 percent for a cell in the "Total" column. |
||||||||||||||||||||||
| Note: Due to rounding, data may not sum to totals. Source: Energy Information Administration, Office of Energy Markets and End Use, Form EIA-871A, C, and E of the 2003 Commercial Buildings Energy Consumption Survey. |
||||||||||||||||||||||