| Released: September, 2008 | ||||||||||||||||||||||
| Table E6. Electricity Consumption (kWh) Intensities by End Use for Non-Mall Buildings, 2003 | ||||||||||||||||||||||
| Electricity Energy Intensity (kWh/square foot) | ||||||||||||||||||||||
| Total | Space Heat- ing |
Cool- ing |
Venti- lation |
Water Heat- ing |
Light- ing |
Cook- ing |
Refrig- eration |
Office Equip- ment |
Com- puters |
Other | ||||||||||||
| All Buildings* ........................ | 14.1 | 0.5 | 1.8 | 1.8 | 0.2 | 5.3 | 0.1 | 1.6 | 0.3 | 0.7 | 1.7 | |||||||||||
| Building Floorspace | ||||||||||||||||||||||
| (Square Feet) | ||||||||||||||||||||||
| 1,001 to 5,000 ......................... | 17.8 | 0.9 | 2.0 | 0.8 | 0.5 | 4.3 | 0.3 | 6.3 | 0.4 | 0.5 | 1.8 | |||||||||||
| 5,001 to 10,000 ....................... | 12.4 | 0.6 | 1.6 | 0.8 | 0.3 | 3.9 | 0.2 | 2.6 | 0.3 | 0.4 | 1.7 | |||||||||||
| 10,001 to 25,000 ..................... | 10.5 | 0.5 | 1.2 | 1.1 | 0.2 | 3.9 | 0.1 | 1.4 | 0.2 | 0.5 | 1.4 | |||||||||||
| 25,001 to 50,000 ..................... | 12.2 | 0.5 | 1.9 | 1.8 | 0.3 | 4.2 | 0.1 | 1.2 | 0.2 | 0.6 | 1.5 | |||||||||||
| 50,001 to 100,000 ................... | 13.1 | 0.5 | 1.9 | 2.1 | 0.2 | 5.1 | 0.1 | 1.0 | 0.2 | 0.6 | 1.5 | |||||||||||
| 100,001 to 200,000 ................. | 15.7 | 0.5 | 2.0 | 2.6 | 0.2 | 6.3 | (*) | 0.8 | Q | 1.0 | 1.8 | |||||||||||
| 200,001 to 500,000 ................. | 15.0 | 0.3 | 2.1 | 2.2 | 0.2 | 6.7 | 0.1 | 0.4 | 0.3 | 0.8 | 1.8 | |||||||||||
| Over 500,000 .......................... | 19.0 | 0.4 | 2.3 | 2.8 | 0.1 | 9.0 | 0.1 | 0.6 | 0.4 | 1.2 | 2.1 | |||||||||||
| Principal Building Activity | ||||||||||||||||||||||
| Education ................................ | 11.0 | 0.5 | 2.2 | 2.5 | 0.3 | 3.4 | (*) | 0.5 | 0.1 | 1.0 | 0.6 | |||||||||||
| Food Sales .............................. | 49.4 | 1.5 | 2.9 | 1.8 | Q | 10.9 | 0.6 | 28.2 | 0.5 | 0.4 | 2.4 | |||||||||||
| Food Service .......................... | 38.4 | 1.8 | 5.0 | 4.3 | 1.8 | 7.5 | 2.4 | 12.3 | 0.3 | 0.3 | 2.6 | |||||||||||
| Health Care ............................. | 22.9 | 0.5 | 3.1 | 3.9 | 0.2 | 9.7 | 0.1 | 0.8 | 0.3 | 0.9 | 3.3 | |||||||||||
| Inpatient ................................ | 27.5 | 0.5 | 3.8 | 5.9 | 0.3 | 11.7 | 0.1 | 0.6 | 0.3 | 1.0 | 3.2 | |||||||||||
| Outpatient ............................. | 16.1 | 0.7 | 2.1 | 1.0 | 0.1 | 6.6 | (*) | 1.0 | 0.4 | 0.8 | 3.5 | |||||||||||
| Lodging ................................... | 13.5 | 0.8 | 1.4 | 0.8 | 0.7 | 7.1 | 0.1 | 0.7 | Q | 0.4 | 1.4 | |||||||||||
| Retail (Other Than Mall)........... | 14.3 | 0.4 | 1.7 | 1.1 | 0.1 | 7.5 | (*) | 1.5 | 0.2 | 0.3 | 1.5 | |||||||||||
| Office ...................................... | 17.3 | 0.8 | 2.4 | 1.5 | 0.2 | 6.8 | (*) | 0.8 | 0.8 | 1.8 | 2.2 | |||||||||||
| Public Assembly ..................... | 12.5 | 0.4 | 2.6 | 4.7 | (*) | 2.0 | (*) | 0.7 | Q | 0.2 | 1.7 | |||||||||||
| Public Order and Safety ......... | 15.3 | 0.5 | 2.1 | 2.8 | 0.9 | 4.8 | (*) | 0.9 | 0.2 | 0.4 | 2.7 | |||||||||||
| Religious Worship ................... | 4.9 | 0.2 | 0.8 | 0.4 | (*) | 1.3 | (*) | 0.5 | (*) | 0.1 | 1.4 | |||||||||||
| Service ................................... | 11.0 | 0.4 | 1.1 | 1.8 | (*) | 4.6 | Q | 0.6 | 0.1 | 0.2 | 2.1 | |||||||||||
| Warehouse and Storage ........ | 7.6 | 0.2 | 0.4 | 0.6 | 0.1 | 4.1 | Q | 1.1 | 0.1 | 0.1 | 0.9 | |||||||||||
| Other ....................................... | 22.5 | 0.4 | 2.7 | 1.8 | 0.1 | 10.1 | Q | 1.8 | Q | 0.9 | 3.7 | |||||||||||
| Vacant .................................... | 2.4 | 0.1 | 0.2 | 0.2 | Q | 0.7 | Q | 0.1 | Q | (*) | 1.1 | |||||||||||
| Year Constructed | ||||||||||||||||||||||
| Before 1920 ............................ | 7.1 | 0.2 | 0.5 | 0.9 | Q | 2.7 | 0.1 | 1.3 | 0.2 | 0.3 | 0.9 | |||||||||||
| 1920 to 1945 ........................... | 9.2 | 0.2 | 0.7 | 1.3 | 0.1 | 4.0 | 0.1 | 1.1 | 0.1 | 0.4 | 1.3 | |||||||||||
| 1946 to 1959 ........................... | 9.9 | 0.4 | 1.1 | 1.5 | 0.2 | 3.7 | 0.1 | 1.1 | 0.2 | 0.5 | 1.2 | |||||||||||
| 1960 to 1969 ........................... | 11.9 | 0.4 | 1.6 | 1.8 | 0.2 | 4.1 | (*) | 1.4 | 0.2 | 0.7 | 1.4 | |||||||||||
| 1970 to 1979 ........................... | 15.9 | 0.7 | 2.0 | 2.1 | 0.3 | 6.1 | 0.1 | 1.6 | 0.3 | 0.8 | 1.9 | |||||||||||
| 1980 to 1989 ........................... | 18.1 | 0.8 | 2.6 | 1.9 | 0.3 | 6.8 | 0.1 | 1.9 | 0.4 | 1.1 | 2.1 | |||||||||||
| 1990 to 1999 ........................... | 16.7 | 0.6 | 2.4 | 2.1 | 0.3 | 6.0 | 0.2 | 2.1 | 0.4 | 0.8 | 1.9 | |||||||||||
| 2000 to 2003 ........................... | 16.2 | 0.5 | 2.5 | 1.8 | 0.2 | 6.4 | 0.2 | 2.1 | 0.2 | 0.5 | 1.8 | |||||||||||
| Census Region and Division | ||||||||||||||||||||||
| Northeast ................................ | 11.5 | 0.5 | 0.8 | 1.5 | 0.1 | 4.7 | 0.1 | 1.3 | 0.3 | 0.7 | 1.5 | |||||||||||
| New England ........................ | 10.8 | 0.5 | 0.6 | 1.2 | 0.2 | 4.2 | 0.1 | 1.9 | 0.2 | 0.6 | 1.3 | |||||||||||
| Middle Atlantic ....................... | 11.7 | 0.4 | 0.9 | 1.6 | 0.1 | 4.9 | (*) | 1.2 | 0.3 | 0.7 | 1.5 | |||||||||||
| Midwest .................................. | 12.9 | 0.8 | 0.9 | 1.8 | 0.2 | 5.0 | 0.1 | 1.6 | 0.3 | 0.6 | 1.7 | |||||||||||
| East North Central ................. | 13.5 | 0.7 | 0.9 | 2.0 | 0.2 | 5.4 | 0.1 | 1.5 | 0.3 | 0.7 | 1.8 | |||||||||||
| West North Central ............... | 11.7 | 0.9 | 1.0 | 1.4 | 0.2 | 4.3 | 0.1 | 1.6 | 0.2 | 0.5 | 1.5 | |||||||||||
| South ...................................... | 16.5 | 0.4 | 3.1 | 2.0 | 0.4 | 5.8 | 0.2 | 2.0 | 0.2 | 0.7 | 1.7 | |||||||||||
| South Atlantic ....................... | 17.4 | 0.5 | 3.0 | 2.1 | 0.5 | 6.3 | 0.2 | 2.1 | 0.3 | 0.9 | 1.7 | |||||||||||
| East South Central ................ | 15.5 | 0.5 | 2.1 | 2.0 | 0.3 | 5.8 | Q | 2.2 | 0.2 | 0.5 | 1.9 | |||||||||||
| West South Central ............... | 15.3 | 0.3 | 3.8 | 1.8 | 0.2 | 5.0 | 0.1 | 1.7 | 0.2 | 0.5 | 1.6 | |||||||||||
| West ....................................... | 13.8 | 0.5 | 1.8 | 1.6 | 0.2 | 5.3 | 0.1 | 1.4 | 0.5 | 0.7 | 1.7 | |||||||||||
| Mountain ............................... | 15.4 | 0.6 | 2.0 | 1.9 | 0.2 | 6.3 | Q | 1.5 | Q | 0.7 | 1.8 | |||||||||||
| Pacific ................................... | 13.0 | 0.4 | 1.6 | 1.5 | 0.2 | 4.8 | 0.1 | 1.4 | Q | 0.8 | 1.7 | |||||||||||
| Climate Zone: 30-Year Average | ||||||||||||||||||||||
| Under 2,000 CDD and -- | ||||||||||||||||||||||
| More than 7,000 HDD ............ | 11.5 | 0.6 | 0.6 | 1.7 | 0.2 | 4.4 | 0.1 | 1.7 | 0.2 | 0.5 | 1.5 | |||||||||||
| 5,500-7,000 HDD .................. | 13.1 | 0.8 | 0.9 | 1.7 | 0.2 | 5.3 | 0.1 | 1.5 | 0.3 | 0.7 | 1.7 | |||||||||||
| 4,000-5,499 HDD .................. | 14.6 | 0.6 | 1.5 | 1.8 | 0.2 | 5.9 | 0.1 | 1.6 | 0.5 | 0.8 | 1.7 | |||||||||||
| Fewer than 4,000 HDD ......... | 14.5 | 0.3 | 2.2 | 1.8 | 0.3 | 5.3 | 0.1 | 1.8 | 0.3 | 0.6 | 1.7 | |||||||||||
| 2,000 CDD or More and -- | ||||||||||||||||||||||
| Fewer than 4,000 HDD ......... | 17.3 | 0.3 | 4.7 | 2.0 | 0.4 | 5.4 | 0.1 | 1.7 | 0.2 | 0.9 | 1.7 | |||||||||||
| Number of Floors | ||||||||||||||||||||||
| One ......................................... | 13.4 | 0.6 | 1.8 | 1.3 | 0.3 | 4.5 | 0.1 | 2.7 | 0.2 | 0.4 | 1.5 | |||||||||||
| Two ........................................ | 12.6 | 0.5 | 1.6 | 1.8 | 0.3 | 4.7 | 0.1 | 1.3 | 0.3 | 0.6 | 1.6 | |||||||||||
| Three ...................................... | 11.4 | 0.5 | 1.3 | 1.6 | 0.2 | 4.5 | 0.1 | 0.9 | 0.3 | 0.6 | 1.5 | |||||||||||
| Four to Nine ............................ | 17.3 | 0.5 | 2.4 | 2.9 | 0.2 | 7.0 | 0.1 | 0.7 | 0.4 | 1.2 | 2.1 | |||||||||||
| Ten or More ............................ | 19.4 | 0.6 | 2.5 | 2.2 | 0.2 | 9.0 | 0.1 | 0.5 | 0.6 | 1.5 | 2.3 | |||||||||||
| Elevators and Escalators | ||||||||||||||||||||||
| (more than one may apply) | ||||||||||||||||||||||
| Any Elevators ......................... | 17.0 | 0.6 | 2.3 | 2.6 | 0.2 | 7.0 | 0.1 | 0.6 | 0.5 | 1.1 | 2.0 | |||||||||||
| Number of Elevators................ | ||||||||||||||||||||||
| One ....................................... | 12.8 | 0.5 | 1.7 | 2.2 | 0.2 | 4.8 | (*) | 0.7 | 0.3 | 0.8 | 1.5 | |||||||||||
| Two to Five ........................... | 17.0 | 0.6 | 2.3 | 2.6 | 0.2 | 6.8 | (*) | 0.6 | 0.5 | 1.2 | 2.0 | |||||||||||
| Six or More ........................... | 22.5 | 0.5 | 3.2 | 3.3 | 0.2 | 10.0 | 0.1 | 0.5 | 0.6 | 1.5 | 2.7 | |||||||||||
| Any Escalators ....................... | 24.1 | 0.6 | 3.9 | 3.7 | 0.2 | 9.9 | Q | 0.5 | Q | 1.4 | 2.7 | |||||||||||
| Number of Workers (main shift) | ||||||||||||||||||||||
| Fewer than 5 .......................... | 7.7 | 0.4 | 0.8 | 0.6 | 0.2 | 2.5 | 0.1 | 1.9 | 0.1 | 0.1 | 1.2 | |||||||||||
| 5 to 9 ....................................... | 11.8 | 0.6 | 1.5 | 1.0 | 0.3 | 3.7 | 0.2 | 2.7 | 0.2 | 0.3 | 1.5 | |||||||||||
| 10 to 19 ................................... | 11.4 | 0.6 | 1.5 | 1.1 | 0.3 | 3.9 | 0.2 | 2.0 | 0.2 | 0.3 | 1.3 | |||||||||||
| 20 to 49 ................................... | 14.0 | 0.5 | 1.9 | 1.9 | 0.3 | 5.1 | 0.1 | 1.8 | 0.4 | 0.6 | 1.6 | |||||||||||
| 50 to 99 ................................... | 14.9 | 0.6 | 2.0 | 2.5 | 0.3 | 5.6 | 0.1 | 1.4 | 0.3 | 0.7 | 1.5 | |||||||||||
| 100 to 249 ............................... | 19.6 | 0.7 | 2.9 | 2.9 | 0.4 | 8.0 | 0.1 | 1.2 | 0.4 | 1.1 | 2.1 | |||||||||||
| 250 or More ............................ | 22.4 | 0.6 | 2.9 | 3.1 | 0.2 | 9.6 | 0.1 | 0.7 | 0.6 | 1.9 | 2.6 | |||||||||||
| Weekly Operating Hours | ||||||||||||||||||||||
| Fewer than 40 ........................ | 4.5 | 0.3 | 0.9 | 0.4 | 0.1 | 1.1 | (*) | 0.6 | (*) | 0.1 | 1.1 | |||||||||||
| 40 to 48 ................................... | 10.1 | 0.6 | 1.7 | 1.1 | 0.2 | 3.4 | (*) | 0.8 | 0.3 | 0.6 | 1.5 | |||||||||||
| 49 to 60 ................................... | 11.2 | 0.4 | 1.5 | 1.3 | 0.1 | 4.3 | (*) | 0.9 | 0.3 | 0.6 | 1.6 | |||||||||||
| 61 to 84 ................................... | 14.1 | 0.5 | 1.8 | 1.9 | 0.2 | 5.2 | 0.1 | 1.8 | 0.3 | 0.7 | 1.6 | |||||||||||
| 85 to 167 ................................. | 22.1 | 0.7 | 2.3 | 3.3 | 0.4 | 7.0 | 0.4 | 5.0 | 0.2 | 0.9 | 1.9 | |||||||||||
| Open Continuously ................. | 21.2 | 0.7 | 2.6 | 2.7 | 0.5 | 9.3 | 0.1 | 1.7 | 0.5 | 0.9 | 2.1 | |||||||||||
| Ownership and Occupancy | ||||||||||||||||||||||
| Nongovernment Owned.......... | 14.0 | 0.6 | 1.7 | 1.4 | 0.2 | 5.5 | 0.1 | 1.9 | 0.3 | 0.6 | 1.7 | |||||||||||
| Owner Occupied .................. | 13.6 | 0.5 | 1.7 | 1.4 | 0.2 | 5.3 | 0.1 | 1.7 | 0.4 | 0.6 | 1.7 | |||||||||||
| Nonowner Occupied ............ | 15.2 | 0.7 | 1.8 | 1.4 | 0.3 | 5.9 | 0.2 | 2.3 | 0.3 | 0.6 | 1.7 | |||||||||||
| Unoccupied ........................... | 1.9 | Q | Q | (*) | Q | 0.5 | (*) | Q | Q | Q | 0.9 | |||||||||||
| Government Owned ............... | 14.1 | 0.5 | 2.2 | 3.1 | 0.3 | 4.7 | 0.1 | 0.7 | 0.2 | 0.9 | 1.5 | |||||||||||
| Federal .................................. | 19.7 | 0.3 | 1.9 | 3.6 | 0.1 | 9.5 | (*) | 0.5 | 0.2 | 0.8 | 2.8 | |||||||||||
| State ..................................... | 15.8 | 0.2 | 2.0 | 4.1 | 0.2 | 4.8 | (*) | 0.7 | 0.2 | 1.6 | 1.9 | |||||||||||
| Local ..................................... | 12.3 | 0.6 | 2.4 | 2.6 | 0.3 | 3.7 | 0.1 | 0.7 | 0.2 | 0.6 | 1.2 | |||||||||||
| Vacancy Status | ||||||||||||||||||||||
| Completely Vacant .................. | 1.8 | Q | Q | (*) | Q | 0.5 | Q | Q | Q | Q | 0.9 | |||||||||||
| Mostly Vacant ......................... | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | |||||||||||
| Partially Vacant ....................... | 13.8 | 0.6 | 1.8 | 1.6 | 0.2 | 5.8 | 0.1 | 0.7 | 0.3 | 1.0 | 1.8 | |||||||||||
| Not At All Vacant .................... | 14.6 | 0.5 | 1.9 | 1.9 | 0.3 | 5.3 | 0.1 | 1.9 | 0.3 | 0.6 | 1.6 | |||||||||||
| Number of Establishments | ||||||||||||||||||||||
| One ......................................... | 14.1 | 0.5 | 1.8 | 1.8 | 0.3 | 5.2 | 0.1 | 1.9 | 0.3 | 0.6 | 1.6 | |||||||||||
| 2 to 5 ....................................... | 13.5 | 0.4 | 1.8 | 1.7 | 0.1 | 5.3 | 0.1 | 1.3 | 0.3 | 0.6 | 1.7 | |||||||||||
| 6 to 10 ..................................... | 17.3 | 0.8 | 2.2 | 2.1 | 0.2 | 6.5 | (*) | 0.7 | 0.4 | 2.4 | 2.0 | |||||||||||
| 11 to 20 ................................... | 14.7 | 0.8 | 2.2 | 1.8 | 0.1 | 5.6 | (*) | Q | 0.3 | 1.0 | 2.0 | |||||||||||
| More than 20 ........................... | 19.6 | 0.6 | 3.2 | 2.5 | 0.2 | 8.0 | (*) | 0.5 | 0.6 | 1.7 | 2.3 | |||||||||||
| Currently Unoccupied ............. | 1.8 | Q | Q | (*) | Q | 0.5 | Q | Q | Q | Q | 0.9 | |||||||||||
| Predominant Exterior | ||||||||||||||||||||||
| Wall Material | ||||||||||||||||||||||
| Brick, Stone or Stucco ............ | 13.7 | 0.5 | 1.9 | 1.9 | 0.3 | 4.8 | 0.1 | 1.6 | 0.3 | 0.7 | 1.6 | |||||||||||
| Concrete (Block or Poured) .... | 14.5 | 0.5 | 2.0 | 1.7 | 0.2 | 5.5 | 0.1 | 2.0 | 0.3 | 0.5 | 1.6 | |||||||||||
| Concrete Panels ..................... | 18.3 | 0.4 | 2.3 | 2.1 | 0.2 | 8.5 | 0.1 | 1.0 | 0.5 | 1.3 | 2.0 | |||||||||||
| Siding or Shingles ................... | 11.0 | 0.7 | 1.2 | 1.0 | 0.3 | 3.6 | 0.1 | 2.1 | 0.3 | 0.4 | 1.3 | |||||||||||
| Metal Panels ............................ | 11.8 | 0.5 | 1.0 | 1.4 | 0.1 | 4.8 | Q | 1.8 | 0.1 | 0.4 | 1.7 | |||||||||||
| Window Glass ........................ | 19.1 | 0.9 | 3.0 | 2.1 | 0.3 | 7.2 | (*) | 0.6 | 0.6 | 1.8 | 2.6 | |||||||||||
| Other ....................................... | 16.7 | 0.9 | 2.5 | 1.7 | 0.1 | 6.7 | 0.2 | 1.1 | 0.4 | 1.1 | 1.9 | |||||||||||
| No One Major Type ................. | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | |||||||||||
| Predominant Roof Material | ||||||||||||||||||||||
| Built-Up ................................... | 14.7 | 0.4 | 2.0 | 1.9 | 0.2 | 5.7 | 0.1 | 1.5 | 0.3 | 0.8 | 1.7 | |||||||||||
| Shingles (Not Wood) ............... | 12.3 | 0.6 | 1.5 | 1.2 | 0.4 | 4.0 | 0.1 | 2.3 | 0.3 | 0.4 | 1.5 | |||||||||||
| Metal Surfacing ....................... | 10.2 | 0.5 | 1.2 | 1.2 | 0.2 | 3.9 | Q | 1.2 | 0.1 | 0.3 | 1.4 | |||||||||||
| Synthetic or Rubber ................ | 17.7 | 0.7 | 2.3 | 2.5 | 0.2 | 6.6 | 0.1 | 1.8 | 0.4 | 1.1 | 2.0 | |||||||||||
| Slate or Tile ............................. | 12.5 | 0.5 | 1.9 | 1.3 | 0.2 | 4.1 | 0.2 | 2.0 | 0.2 | 0.5 | 1.5 | |||||||||||
| Wooden Materials ................... | 12.2 | 0.7 | 1.9 | 1.3 | 0.3 | 4.7 | (*) | 1.4 | 0.2 | 0.4 | 1.3 | |||||||||||
| Concrete ................................. | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | |||||||||||
| Other ....................................... | 20.4 | 0.2 | 2.9 | 1.6 | Q | 11.0 | Q | 1.7 | 0.1 | 0.6 | 2.0 | |||||||||||
| No One Major Type ................. | 10.4 | Q | 1.4 | 1.9 | Q | 3.2 | Q | Q | 0.2 | Q | 1.4 | |||||||||||
| Renovations in Buildings | ||||||||||||||||||||||
| Constructed Before 1980 | ||||||||||||||||||||||
| (more than one may apply) | ||||||||||||||||||||||
| Any Type of Renovation | ||||||||||||||||||||||
| Since 1980 ............................. | 13.0 | 0.5 | 1.4 | 1.9 | 0.2 | 5.0 | 0.1 | 1.5 | 0.3 | 0.7 | 1.5 | |||||||||||
| Addition or Annex ................ | 14.1 | 0.6 | 1.6 | 2.5 | 0.2 | 5.4 | 0.1 | 1.4 | 0.2 | 0.6 | 1.6 | |||||||||||
| Reduction In Floorspace ...... | 15.2 | 0.5 | 1.5 | 2.6 | 0.2 | 6.4 | 0.1 | 0.7 | 0.3 | 0.9 | 2.0 | |||||||||||
| Cosmetic Improvements ....... | 13.5 | 0.5 | 1.4 | 1.9 | 0.2 | 5.2 | 0.1 | 1.6 | 0.3 | 0.8 | 1.5 | |||||||||||
| Wall or Roof Replacement ... | 12.6 | 0.4 | 1.4 | 1.9 | 0.2 | 5.1 | 0.1 | 1.0 | 0.2 | 0.8 | 1.4 | |||||||||||
| Interior Wall | ||||||||||||||||||||||
| Re-Configuration ................ | 13.8 | 0.5 | 1.5 | 2.1 | 0.2 | 5.6 | 0.1 | 1.1 | 0.3 | 0.8 | 1.7 | |||||||||||
| HVAC Equipment Upgrade.... | 14.4 | 0.6 | 1.6 | 2.2 | 0.2 | 5.6 | 0.1 | 1.2 | 0.3 | 0.9 | 1.6 | |||||||||||
| Lighting Upgrade .................. | 13.6 | 0.5 | 1.4 | 2.1 | 0.2 | 5.3 | 0.1 | 1.4 | 0.3 | 0.8 | 1.6 | |||||||||||
| Window Replacement .......... | 11.7 | 0.4 | 1.1 | 1.7 | 0.2 | 4.7 | 0.1 | 1.2 | 0.2 | 0.8 | 1.4 | |||||||||||
| Plumbing System Upgrade ... | 12.9 | 0.4 | 1.3 | 2.1 | 0.2 | 5.3 | 0.1 | 1.0 | 0.2 | 0.8 | 1.5 | |||||||||||
| Insulation Upgrade ............... | 12.7 | 0.4 | 1.5 | 2.2 | 0.2 | 4.7 | 0.1 | 1.1 | 0.2 | 0.8 | 1.5 | |||||||||||
| Other Renovation ................. | 9.0 | 0.4 | 0.6 | 1.3 | Q | 4.0 | 0.1 | 1.0 | 0.1 | 0.3 | 1.1 | |||||||||||
| No Renovations Since 1980.... | 10.5 | 0.4 | 1.3 | 1.4 | 0.2 | 4.0 | 0.1 | 1.3 | 0.2 | 0.4 | 1.4 | |||||||||||
| Building Newer than 1980 ...... | 17.1 | 0.7 | 2.5 | 2.0 | 0.3 | 6.4 | 0.1 | 2.0 | 0.4 | 0.9 | 1.9 | |||||||||||
| Energy Sources (more than | ||||||||||||||||||||||
| one may apply) | ||||||||||||||||||||||
| Electricity ................................ | 14.1 | 0.5 | 1.8 | 1.8 | 0.2 | 5.3 | 0.1 | 1.6 | 0.3 | 0.7 | 1.7 | |||||||||||
| Natural Gas ............................. | 14.6 | 0.4 | 1.8 | 2.0 | 0.2 | 5.7 | 0.1 | 1.6 | 0.3 | 0.7 | 1.7 | |||||||||||
| Fuel Oil .................................... | 16.5 | 0.6 | 2.1 | 2.3 | 0.2 | 7.0 | 0.1 | 0.8 | 0.5 | 1.0 | 2.0 | |||||||||||
| District Heat ............................ | 18.0 | 0.2 | 1.3 | 3.7 | 0.2 | 7.9 | (*) | 0.6 | 0.2 | 1.6 | 2.3 | |||||||||||
| District Chilled Water ............... | 19.7 | 0.2 | 1.6 | 5.0 | 0.2 | 7.0 | 0.1 | 0.8 | 0.3 | 2.1 | 2.4 | |||||||||||
| Propane .................................. | 14.0 | 0.4 | 1.5 | 1.7 | 0.2 | 5.8 | 0.1 | 2.1 | 0.2 | 0.4 | 1.7 | |||||||||||
| Other ....................................... | 16.4 | 0.4 | 1.6 | 3.0 | 0.1 | 6.4 | 0.1 | 1.4 | Q | 0.8 | 2.1 | |||||||||||
| Space-Heating Energy Sources | ||||||||||||||||||||||
| Electricity ................................ | 15.9 | 1.2 | 2.3 | 1.6 | 0.4 | 5.9 | 0.1 | 1.7 | 0.4 | 0.7 | 1.7 | |||||||||||
| Electricity Main ...................... | 16.6 | 1.7 | 2.8 | 1.3 | 0.5 | 5.6 | 0.1 | 2.0 | 0.4 | 0.7 | 1.6 | |||||||||||
| Electricity Secondary ............ | 15.1 | 0.5 | 1.7 | 2.0 | 0.2 | 6.2 | 0.1 | 1.2 | 0.4 | 0.8 | 1.9 | |||||||||||
| Other Excluding Electricity ...... | 13.0 | (*) | 1.4 | 2.1 | 0.1 | 5.1 | 0.1 | 1.6 | 0.2 | 0.7 | 1.7 | |||||||||||
| Buildings without Heating ....... | 8.2 | (*) | 1.8 | 0.7 | 0.1 | 2.6 | 0.1 | 1.7 | 0.1 | 0.2 | 1.0 | |||||||||||
| Primary Space-Heating | ||||||||||||||||||||||
| Energy Source | ||||||||||||||||||||||
| Electricity ................................ | 16.6 | 1.7 | 2.8 | 1.3 | 0.5 | 5.6 | 0.1 | 2.0 | 0.4 | 0.7 | 1.6 | |||||||||||
| Natural Gas ............................. | 13.9 | 0.2 | 1.7 | 1.9 | 0.2 | 5.5 | 0.1 | 1.6 | 0.3 | 0.7 | 1.8 | |||||||||||
| Fuel Oil .................................... | 5.9 | 0.1 | 0.4 | 1.0 | 0.1 | 2.2 | (*) | 1.0 | 0.1 | 0.3 | 0.7 | |||||||||||
| District Heat ............................ | 18.5 | 0.1 | 1.2 | 3.9 | 0.2 | 8.1 | (*) | 0.6 | 0.3 | 1.6 | 2.4 | |||||||||||
| Propane .................................. | 10.5 | 0.2 | 1.1 | 1.3 | 0.2 | 2.7 | Q | 2.9 | Q | Q | 1.5 | |||||||||||
| Other ....................................... | 12.6 | 0.1 | 0.8 | 1.5 | 0.1 | 6.0 | (*) | 1.8 | 0.2 | Q | 1.8 | |||||||||||
| Cooling Energy Source | ||||||||||||||||||||||
| Electricity ................................ | 15.0 | 0.6 | 2.1 | 1.8 | 0.3 | 5.6 | 0.1 | 1.8 | 0.3 | 0.7 | 1.7 | |||||||||||
| Other Excluding Electricity ...... | 17.5 | Q | (*) | 4.7 | 0.2 | 7.0 | (*) | 0.7 | 0.3 | 2.3 | 2.1 | |||||||||||
| Buildings without Cooling ........ | 4.8 | 0.2 | (*) | 0.7 | (*) | 2.2 | (*) | 0.6 | (*) | 0.1 | 0.9 | |||||||||||
| Water-Heating Energy Source | ||||||||||||||||||||||
| Electricity ................................ | 14.6 | 0.8 | 2.1 | 1.5 | 0.6 | 5.2 | 0.1 | 1.7 | 0.3 | 0.7 | 1.7 | |||||||||||
| Other Excluding Electricity ...... | 15.4 | 0.4 | 1.9 | 2.3 | (*) | 6.0 | 0.1 | 1.8 | 0.3 | 0.8 | 1.8 | |||||||||||
| Bldgs without Water Heating .. | 6.2 | 0.2 | 0.7 | 0.6 | (*) | 2.7 | Q | 0.8 | 0.1 | 0.1 | 1.0 | |||||||||||
| Cooking Energy Source | ||||||||||||||||||||||
| Electricity ................................ | 18.9 | 0.8 | 2.6 | 2.8 | 0.5 | 6.5 | 0.5 | 2.3 | 0.3 | 0.8 | 1.7 | |||||||||||
| Other Excluding Electricity ...... | 17.1 | 0.5 | 2.5 | 2.5 | 0.3 | 6.2 | (*) | 2.6 | 0.3 | 0.6 | 1.7 | |||||||||||
| Buildings without Cooking ....... | 11.8 | 0.5 | 1.5 | 1.3 | 0.2 | 4.7 | (*) | 1.2 | 0.3 | 0.7 | 1.6 | |||||||||||
| Energy End Uses (more than | ||||||||||||||||||||||
| one may apply) | ||||||||||||||||||||||
| Buildings with Space Heating . | 14.4 | 0.6 | 1.8 | 1.8 | 0.3 | 5.4 | 0.1 | 1.6 | 0.3 | 0.7 | 1.7 | |||||||||||
| Buildings with Cooling ............. | 15.1 | 0.6 | 2.0 | 1.9 | 0.3 | 5.6 | 0.1 | 1.8 | 0.3 | 0.8 | 1.7 | |||||||||||
| Buildings with Water Heating .. | 15.0 | 0.6 | 2.0 | 1.9 | 0.3 | 5.6 | 0.1 | 1.7 | 0.3 | 0.8 | 1.7 | |||||||||||
| Buildings with Cooking ............ | 18.2 | 0.7 | 2.5 | 2.7 | 0.4 | 6.4 | 0.3 | 2.4 | 0.3 | 0.7 | 1.7 | |||||||||||
| Buildings with Manufacturing . | 13.2 | 0.4 | 0.9 | 1.6 | Q | 6.0 | Q | 0.9 | 0.2 | 0.6 | 2.3 | |||||||||||
| Buildings with Electricity | ||||||||||||||||||||||
| Generation ............................. | 20.3 | 0.7 | 2.7 | 3.0 | 0.3 | 8.4 | 0.1 | 1.0 | 0.6 | 1.3 | 2.4 | |||||||||||
| Percent of Floorspace Heated | ||||||||||||||||||||||
| Not Heated .............................. | 8.2 | (*) | 1.8 | 0.7 | 0.1 | 2.6 | 0.1 | 1.7 | 0.1 | 0.2 | 1.0 | |||||||||||
| 1 to 50 ..................................... | 8.0 | 0.2 | 0.6 | 0.8 | 0.2 | 3.0 | Q | 1.7 | Q | 0.2 | 1.1 | |||||||||||
| 51 to 99 ................................... | 14.3 | 0.5 | 1.8 | 1.8 | 0.2 | 5.5 | 0.1 | 2.0 | 0.2 | 0.6 | 1.6 | |||||||||||
| 100 .......................................... | 15.4 | 0.6 | 2.0 | 2.0 | 0.3 | 5.8 | 0.1 | 1.6 | 0.3 | 0.8 | 1.8 | |||||||||||
| Percent of Floorspace Cooled | ||||||||||||||||||||||
| Not Cooled .............................. | 4.8 | 0.2 | (*) | 0.7 | (*) | 2.2 | (*) | 0.6 | (*) | 0.1 | 0.9 | |||||||||||
| 1 to 50 ..................................... | 7.8 | 0.3 | 0.4 | 1.0 | 0.1 | 3.5 | Q | 1.1 | 0.1 | 0.2 | 1.1 | |||||||||||
| 51 to 99 ................................... | 16.5 | 0.7 | 2.1 | 2.2 | 0.2 | 6.1 | 0.1 | 2.3 | 0.3 | 0.8 | 1.8 | |||||||||||
| 100 .......................................... | 18.8 | 0.7 | 3.0 | 2.3 | 0.4 | 6.8 | 0.2 | 1.9 | 0.5 | 1.0 | 2.1 | |||||||||||
| Percent Lit When Open | ||||||||||||||||||||||
| Zero ........................................ | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | |||||||||||
| 1 to 50 ..................................... | 6.5 | 0.3 | 0.9 | 0.8 | 0.2 | 1.8 | 0.1 | 0.8 | Q | 0.2 | 1.1 | |||||||||||
| 51 to 99 ................................... | 14.3 | 0.5 | 1.9 | 2.0 | 0.3 | 5.3 | 0.1 | 1.4 | 0.3 | 0.9 | 1.7 | |||||||||||
| 100 .......................................... | 17.0 | 0.6 | 2.2 | 2.1 | 0.3 | 6.7 | 0.1 | 2.1 | 0.3 | 0.8 | 1.8 | |||||||||||
| Building Never Open/ | ||||||||||||||||||||||
| Electricity Not Used ................ | 2.1 | Q | 0.2 | 0.1 | Q | 0.6 | Q | 0.1 | Q | Q | 1.0 | |||||||||||
| Percent Lit When Closed | ||||||||||||||||||||||
| Zero ........................................ | 9.2 | 0.4 | 1.2 | 1.2 | 0.1 | 2.9 | 0.1 | 1.2 | 0.2 | 0.5 | 1.4 | |||||||||||
| 1 to 50 ..................................... | 13.3 | 0.5 | 1.8 | 1.7 | 0.2 | 4.6 | 0.1 | 1.7 | 0.3 | 0.7 | 1.6 | |||||||||||
| 51 to 100 ................................. | 21.7 | 0.8 | 2.2 | 2.0 | 0.3 | 10.4 | 0.2 | 3.4 | 0.2 | 0.6 | 1.5 | |||||||||||
| Building Never Closed/ | ||||||||||||||||||||||
| Electricity Not Used ................ | 21.2 | 0.7 | 2.6 | 2.7 | 0.5 | 9.3 | 0.1 | 1.7 | 0.5 | 0.9 | 2.1 | |||||||||||
| Heating Equipment (more | ||||||||||||||||||||||
| than one may apply) | ||||||||||||||||||||||
| Heat Pumps ............................. | 17.4 | 0.9 | 2.9 | 1.8 | 0.4 | 6.7 | 0.1 | 1.5 | 0.4 | 0.8 | 1.8 | |||||||||||
| Packaged Heat Pumps .......... | 19.3 | 1.0 | 3.3 | 1.8 | 0.4 | 7.6 | 0.1 | 1.8 | 0.5 | 0.9 | 2.0 | |||||||||||
| Split-System Heat Pumps ...... | 15.4 | 0.7 | 2.7 | 2.1 | 0.4 | 5.7 | Q | 1.3 | 0.2 | 0.5 | 1.7 | |||||||||||
| Individual Room Heat Pumps . | 16.1 | 0.9 | 2.8 | 1.8 | 0.5 | 6.5 | 0.1 | 0.8 | 0.2 | 0.9 | 1.6 | |||||||||||
| Furnaces ................................ | 11.4 | 0.5 | 1.2 | 1.3 | 0.2 | 4.3 | 0.1 | 1.8 | 0.2 | 0.4 | 1.4 | |||||||||||
| Individual Space Heaters ........ | 13.2 | 0.9 | 1.4 | 1.5 | 0.3 | 5.3 | 0.1 | 1.4 | 0.2 | 0.6 | 1.5 | |||||||||||
| District Heat ............................ | 18.0 | 0.1 | 1.2 | 3.8 | 0.2 | 7.9 | (*) | 0.6 | 0.3 | 1.6 | 2.3 | |||||||||||
| Boilers ..................................... | 14.5 | 0.4 | 1.8 | 2.4 | 0.2 | 5.8 | 0.1 | 0.8 | 0.3 | 0.8 | 1.8 | |||||||||||
| Packaged Heating Units .......... | 17.2 | 0.8 | 2.5 | 1.9 | 0.3 | 6.2 | 0.2 | 2.2 | 0.4 | 0.8 | 1.8 | |||||||||||
| Other ....................................... | 15.2 | 0.9 | 1.9 | 1.8 | 0.3 | 5.8 | 0.1 | 1.7 | 0.2 | 0.7 | 1.8 | |||||||||||
| Cooling Equipment (more | ||||||||||||||||||||||
| than one may apply) | ||||||||||||||||||||||
| Residential-Type Central | ||||||||||||||||||||||
| Air Conditioners ..................... | 12.1 | 0.5 | 1.6 | 1.8 | 0.3 | 4.2 | 0.1 | 1.6 | 0.2 | 0.4 | 1.5 | |||||||||||
| Heat Pumps ............................. | 17.7 | 0.8 | 3.0 | 1.8 | 0.4 | 6.8 | 0.1 | 1.8 | 0.4 | 0.8 | 1.9 | |||||||||||
| Packaged Heat Pumps .......... | 19.4 | 1.0 | 3.2 | 1.7 | 0.4 | 7.7 | 0.1 | 1.9 | 0.5 | 0.9 | 2.0 | |||||||||||
| Split-System Heat Pumps ...... | 15.7 | 0.6 | 2.7 | 2.1 | 0.4 | 5.6 | Q | 1.5 | 0.2 | 0.6 | 1.8 | |||||||||||
| Individual Room Heat Pumps . | 17.1 | 0.8 | 3.0 | 1.9 | 0.5 | 6.8 | 0.1 | 1.1 | 0.3 | 0.8 | 1.7 | |||||||||||
| Individual Air Conditioners ...... | 11.2 | 0.5 | 1.5 | 1.5 | 0.3 | 4.6 | 0.1 | 1.0 | 0.2 | 0.4 | 1.2 | |||||||||||
| District Chilled Water ............... | 19.7 | 0.2 | 1.6 | 5.0 | 0.2 | 7.0 | 0.1 | 0.8 | 0.3 | 2.1 | 2.4 | |||||||||||
| Central Chillers ........................ | 21.1 | 0.6 | 3.1 | 3.5 | 0.3 | 8.5 | 0.1 | 0.7 | 0.6 | 1.3 | 2.5 | |||||||||||
| Packaged Air Conditioning | ||||||||||||||||||||||
| Units ....................................... | 15.4 | 0.6 | 2.1 | 1.7 | 0.3 | 5.8 | 0.1 | 2.0 | 0.3 | 0.7 | 1.7 | |||||||||||
| Swamp Coolers ...................... | 14.1 | 0.4 | 1.6 | 1.7 | 0.4 | 5.3 | 0.2 | 2.3 | 0.2 | 0.4 | 1.7 | |||||||||||
| Other ....................................... | 18.0 | 0.6 | 2.7 | 2.5 | 0.1 | 6.8 | 0.1 | Q | 0.3 | 0.9 | 1.9 | |||||||||||
| Main Equipment Replaced Since | ||||||||||||||||||||||
| 1990 (more than one may apply) | ||||||||||||||||||||||
| Heating .................................... | 12.8 | 0.6 | 1.6 | 1.5 | 0.3 | 4.6 | 0.1 | 1.5 | 0.3 | 0.7 | 1.6 | |||||||||||
| Cooling .................................... | 13.6 | 0.6 | 1.7 | 1.7 | 0.3 | 5.1 | 0.1 | 1.5 | 0.3 | 0.8 | 1.6 | |||||||||||
| Water Heating Equipment | ||||||||||||||||||||||
| Centralized System ................. | 14.9 | 0.6 | 1.9 | 1.9 | 0.3 | 5.3 | 0.1 | 2.1 | 0.3 | 0.7 | 1.7 | |||||||||||
| Distributed System .................. | 12.3 | 0.5 | 1.9 | 1.4 | 0.2 | 4.6 | 0.1 | 1.3 | 0.2 | 0.6 | 1.5 | |||||||||||
| Combination of Centralized | ||||||||||||||||||||||
| and Distributed System .......... | 18.6 | 0.6 | 2.5 | 2.5 | 0.3 | 7.7 | 0.1 | 1.0 | 0.5 | 1.2 | 2.0 | |||||||||||
| Lighting Equipment Types | ||||||||||||||||||||||
| (more than one may apply) | ||||||||||||||||||||||
| Incandescent .......................... | 15.3 | 0.6 | 2.0 | 2.0 | 0.3 | 6.1 | 0.1 | 1.5 | 0.3 | 0.8 | 1.7 | |||||||||||
| Standard Fluorescent ............. | 14.5 | 0.5 | 1.9 | 1.9 | 0.2 | 5.4 | 0.1 | 1.7 | 0.3 | 0.7 | 1.7 | |||||||||||
| Compact Fluorescent .............. | 17.7 | 0.6 | 2.3 | 2.5 | 0.3 | 6.9 | 0.1 | 1.5 | 0.4 | 0.9 | 2.0 | |||||||||||
| High Intensity Discharge ......... | 16.0 | 0.5 | 1.9 | 2.4 | 0.2 | 6.7 | 0.1 | 1.2 | 0.3 | 0.9 | 1.8 | |||||||||||
| Halogen ................................... | 17.7 | 0.7 | 2.2 | 2.3 | 0.3 | 7.5 | 0.1 | 1.6 | 0.4 | 0.8 | 1.9 | |||||||||||
| Other ....................................... | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | |||||||||||
| Refrigeration Equipment | ||||||||||||||||||||||
| (more than one may apply) | ||||||||||||||||||||||
| Any Refrigeration.................... | 15.3 | 0.6 | 2.0 | 1.9 | 0.3 | 5.7 | 0.1 | 2.0 | 0.3 | 0.8 | 1.7 | |||||||||||
| Commercial Refrigeration ...... | 19.6 | 0.7 | 2.6 | 2.6 | 0.3 | 7.1 | 0.2 | 3.1 | 0.3 | 0.8 | 1.9 | |||||||||||
| Walk-In Units ....................... | 21.5 | 0.7 | 2.8 | 2.9 | 0.4 | 7.8 | 0.3 | 3.6 | 0.3 | 0.8 | 1.9 | |||||||||||
| Cases or Cabinets .............. | 20.7 | 0.7 | 2.8 | 2.7 | 0.3 | 7.5 | 0.2 | 3.4 | 0.3 | 0.8 | 1.9 | |||||||||||
| Residential-Type Units .......... | 13.3 | 0.5 | 1.8 | 1.8 | 0.2 | 5.1 | 0.1 | 1.2 | 0.3 | 0.7 | 1.6 | |||||||||||
| Vending Machines ................ | 16.5 | 0.6 | 2.2 | 2.3 | 0.3 | 6.5 | 0.1 | 1.5 | 0.4 | 0.9 | 1.8 | |||||||||||
| No Refrigeration ...................... | 7.5 | 0.3 | 1.1 | 1.0 | 0.1 | 3.2 | Q | (*) | 0.1 | 0.3 | 1.4 | |||||||||||
| Office Equipment (more | ||||||||||||||||||||||
| than one may apply) | ||||||||||||||||||||||
| Computers .............................. | 15.0 | 0.6 | 2.0 | 1.9 | 0.3 | 5.7 | 0.1 | 1.6 | 0.3 | 0.8 | 1.7 | |||||||||||
| With Flat Screen Monitors ..... | 17.6 | 0.6 | 2.4 | 2.5 | 0.2 | 6.8 | 0.1 | 1.2 | 0.5 | 1.2 | 2.1 | |||||||||||
| Dedicated Servers .................. | 16.4 | 0.6 | 2.2 | 2.3 | 0.2 | 6.4 | 0.1 | 1.3 | 0.5 | 1.0 | 1.9 | |||||||||||
| Laser Printers ......................... | 13.8 | 0.6 | 1.8 | 1.8 | 0.2 | 5.1 | 0.1 | 1.6 | 0.3 | 0.7 | 1.6 | |||||||||||
| Inkjet Printers .......................... | 16.6 | 0.6 | 2.3 | 2.2 | 0.3 | 6.5 | 0.1 | 1.4 | 0.4 | 0.9 | 1.9 | |||||||||||
| FAX Machines ........................ | 15.1 | 0.6 | 2.0 | 2.0 | 0.2 | 5.8 | 0.1 | 1.5 | 0.3 | 0.8 | 1.7 | |||||||||||
| Photocopiers ........................... | 15.0 | 0.5 | 2.0 | 2.1 | 0.2 | 5.9 | 0.1 | 1.2 | 0.4 | 0.9 | 1.7 | |||||||||||
| Number of Computers | ||||||||||||||||||||||
| None ....................................... | 7.6 | 0.3 | 0.8 | 0.5 | 0.2 | 2.5 | 0.1 | 2.1 | (*) | (*) | 1.1 | |||||||||||
| 1 to 4 ....................................... | 12.4 | 0.6 | 1.4 | 1.1 | 0.3 | 3.9 | 0.2 | 3.1 | 0.1 | 0.1 | 1.4 | |||||||||||
| 5 to 9 ....................................... | 11.2 | 0.6 | 1.6 | 1.1 | 0.2 | 4.1 | 0.1 | 1.6 | 0.2 | 0.3 | 1.4 | |||||||||||
| 10 to 19 ................................... | 12.6 | 0.5 | 1.7 | 1.5 | 0.2 | 4.8 | 0.1 | 1.8 | 0.2 | 0.4 | 1.6 | |||||||||||
| 20 to 49 ................................... | 16.1 | 0.5 | 2.1 | 2.2 | 0.3 | 6.3 | Q | 1.5 | Q | 0.6 | 2.0 | |||||||||||
| 50 to 99 ................................... | 14.1 | 0.5 | 2.1 | 2.1 | 0.3 | 5.9 | (*) | 0.6 | 0.3 | 0.8 | 1.6 | |||||||||||
| 100 to 249 ............................... | 16.1 | 0.7 | 2.4 | 2.7 | 0.3 | 6.2 | (*) | 0.7 | 0.3 | 1.1 | 1.8 | |||||||||||
| 250 or More ............................ | 21.2 | 0.6 | 2.8 | 3.2 | 0.2 | 8.6 | 0.1 | 0.6 | 0.7 | 2.1 | 2.3 | |||||||||||
| Number of Dedicated Servers | ||||||||||||||||||||||
| None ....................................... | 10.9 | 0.4 | 1.4 | 1.1 | 0.2 | 3.8 | 0.1 | 2.1 | 0.1 | 0.3 | 1.4 | |||||||||||
| 1 to 4 ....................................... | 14.2 | 0.6 | 1.9 | 1.9 | 0.2 | 5.5 | 0.1 | 1.6 | 0.2 | 0.6 | 1.6 | |||||||||||
| 5 to 9 ....................................... | 19.0 | 0.6 | 2.8 | 3.0 | 0.3 | 7.6 | Q | 0.9 | 0.5 | 1.3 | 2.1 | |||||||||||
| 10 to 19 ................................... | 20.9 | 0.5 | 2.4 | 3.4 | 0.2 | 8.1 | (*) | 1.1 | 0.5 | 2.2 | 2.4 | |||||||||||
| 20 to 49 ................................... | 20.7 | 0.5 | 3.6 | 2.9 | 0.2 | 8.0 | 0.1 | 0.6 | 0.7 | 1.6 | 2.4 | |||||||||||
| 50 or More .............................. | 23.4 | 0.7 | 2.1 | 2.4 | 0.2 | 9.8 | Q | 0.7 | 2.3 | 2.3 | 2.7 | |||||||||||
| Number of Photocopiers | ||||||||||||||||||||||
| None ....................................... | 11.6 | 0.6 | 1.3 | 1.0 | 0.3 | 3.7 | 0.2 | 2.9 | 0.1 | 0.2 | 1.4 | |||||||||||
| One ......................................... | 11.2 | 0.5 | 1.4 | 1.3 | 0.2 | 4.2 | 0.1 | 1.7 | 0.2 | 0.3 | 1.4 | |||||||||||
| 2 to 4 ....................................... | 13.7 | 0.5 | 1.9 | 2.0 | 0.2 | 5.3 | 0.1 | 1.2 | 0.4 | 0.7 | 1.6 | |||||||||||
| 5 to 9 ....................................... | 17.2 | 0.6 | 2.4 | 2.8 | 0.2 | 6.5 | (*) | 0.8 | 0.4 | 1.6 | 2.0 | |||||||||||
| 10 or More .............................. | 21.2 | 0.6 | 3.0 | 3.0 | 0.2 | 9.0 | 0.1 | 0.6 | 0.7 | 1.6 | 2.4 | |||||||||||
| Energy-Related Space Functions | ||||||||||||||||||||||
| (more than one may apply) | ||||||||||||||||||||||
| Commercial Food Preparation.. | 18.2 | 0.7 | 2.5 | 2.7 | 0.4 | 6.4 | 0.3 | 2.4 | 0.3 | 0.7 | 1.7 | |||||||||||
| Activities with Large | ||||||||||||||||||||||
| Amounts of Hot Water ........... | 17.6 | 0.7 | 2.4 | 2.6 | 0.4 | 7.0 | 0.2 | 1.5 | 0.3 | 0.8 | 1.8 | |||||||||||
| Separate Computer Area ........ | 16.9 | 0.6 | 2.4 | 2.5 | 0.3 | 6.7 | 0.1 | 0.9 | 0.5 | 1.1 | 1.8 | |||||||||||
| HVAC Conservation Features | ||||||||||||||||||||||
| (more than one may apply) | ||||||||||||||||||||||
| Variable Air-Volume System... | 19.0 | 0.7 | 2.7 | 2.6 | 0.3 | 7.5 | 0.1 | 1.1 | 0.5 | 1.3 | 2.3 | |||||||||||
| Economizer Cycle ................... | 19.5 | 0.7 | 2.5 | 2.9 | 0.3 | 7.7 | 0.1 | 1.3 | 0.5 | 1.3 | 2.2 | |||||||||||
| HVAC Maintenance ................ | 15.5 | 0.6 | 2.1 | 2.1 | 0.3 | 5.9 | 0.1 | 1.6 | 0.3 | 0.8 | 1.8 | |||||||||||
| Energy Management and | ||||||||||||||||||||||
| Control System (EMCS) ......... | 17.9 | 0.6 | 2.7 | 3.0 | 0.3 | 6.9 | 0.1 | 0.8 | 0.5 | 1.1 | 2.0 | |||||||||||
| Window and Interior Lighting | ||||||||||||||||||||||
| Features (more than one | ||||||||||||||||||||||
| may apply) | ||||||||||||||||||||||
| Multipaned Windows .............. | 15.3 | 0.7 | 1.8 | 2.0 | 0.3 | 5.9 | 0.1 | 1.7 | 0.3 | 0.7 | 1.8 | |||||||||||
| Tinted Window Glass ............. | 16.6 | 0.5 | 2.3 | 2.2 | 0.2 | 6.6 | 0.1 | 1.3 | 0.4 | 0.9 | 2.0 | |||||||||||
| Reflective Window Glass ....... | 17.9 | 0.7 | 2.6 | 2.4 | 0.3 | 7.3 | 0.1 | 1.1 | 0.4 | 1.0 | 2.1 | |||||||||||
| External Overhangs | ||||||||||||||||||||||
| or Awnings ............................ | 16.4 | 0.6 | 2.0 | 2.1 | 0.3 | 5.8 | 0.2 | 2.4 | 0.4 | 0.8 | 1.7 | |||||||||||
| Skylights or Atriums ................ | 15.1 | 0.5 | 1.9 | 2.2 | 0.2 | 6.4 | 0.1 | 0.8 | 0.5 | 0.8 | 1.8 | |||||||||||
| Daylighting Sensors ................ | 21.1 | 0.6 | 2.9 | 3.0 | 0.2 | 8.1 | 0.1 | 1.3 | Q | 1.2 | 2.4 | |||||||||||
| Specular Reflectors ................ | 16.7 | 0.6 | 2.2 | 2.3 | 0.3 | 6.7 | 0.1 | 1.3 | 0.4 | 0.9 | 2.0 | |||||||||||
| Electronic Ballasts .................. | 15.6 | 0.6 | 2.1 | 2.1 | 0.3 | 5.9 | 0.1 | 1.6 | 0.3 | 0.8 | 1.8 | |||||||||||
| Energy Management and | ||||||||||||||||||||||
| Control System (EMCS) | ||||||||||||||||||||||
| For Lighting ............................ | 19.1 | 0.6 | 2.9 | 2.7 | 0.3 | 7.6 | 0.1 | 0.9 | Q | 1.2 | 2.1 | |||||||||||
| Equipment Usage Reduced | ||||||||||||||||||||||
| When Building Not In Full Use | ||||||||||||||||||||||
| (more than one may apply) | ||||||||||||||||||||||
| Heating .................................... | 13.2 | 0.5 | 1.8 | 1.8 | 0.2 | 4.9 | 0.1 | 1.3 | 0.3 | 0.7 | 1.6 | |||||||||||
| Cooling .................................... | 13.8 | 0.5 | 1.9 | 1.9 | 0.2 | 5.1 | 0.1 | 1.3 | 0.3 | 0.8 | 1.6 | |||||||||||
| Lighting ................................... | 12.5 | 0.5 | 1.7 | 1.6 | 0.2 | 4.3 | 0.1 | 1.7 | 0.2 | 0.6 | 1.6 | |||||||||||
| Office Equipment .................... | 10.9 | 0.4 | 1.6 | 1.5 | 0.2 | 3.9 | 0.1 | 1.2 | 0.2 | 0.4 | 1.4 | |||||||||||
| Annual Consumption | ||||||||||||||||||||||
| (kilowatthours) | ||||||||||||||||||||||
| 10,000 or Less ....................... | 1.3 | (*) | 0.1 | 0.1 | (*) | 0.4 | (*) | 0.2 | (*) | (*) | 0.4 | |||||||||||
| 10,001 to 50,000 ..................... | 4.9 | 0.2 | 0.6 | 0.3 | 0.1 | 1.7 | (*) | 0.7 | 0.1 | 0.1 | 0.9 | |||||||||||
| 50,001 to 100,000 ................... | 8.0 | 0.4 | 1.0 | 0.6 | 0.2 | 2.5 | 0.1 | 1.6 | 0.2 | 0.3 | 1.2 | |||||||||||
| 100,001 to 500,000 ................. | 13.0 | 0.6 | 1.5 | 1.3 | 0.3 | 4.2 | 0.2 | 2.7 | 0.2 | 0.5 | 1.5 | |||||||||||
| 500,001 to 1,000,000 .............. | 14.4 | 0.6 | 2.2 | 1.9 | 0.4 | 5.0 | 0.1 | 1.9 | 0.2 | 0.6 | 1.5 | |||||||||||
| 1,000,001 to 5,000,000 ........... | 20.3 | 0.7 | 2.8 | 3.2 | 0.3 | 7.7 | 0.1 | 1.7 | 0.4 | 1.2 | 2.2 | |||||||||||
| Over 5,000,000 ....................... | 24.7 | 0.5 | 3.2 | 3.3 | 0.2 | 11.4 | 0.1 | 0.9 | 0.7 | 1.4 | 2.8 | |||||||||||
| Provider of Purchased | ||||||||||||||||||||||
| Electricity (more than | ||||||||||||||||||||||
| one may apply) | ||||||||||||||||||||||
| Local Utility .............................. | 13.7 | 0.5 | 1.8 | 1.7 | 0.2 | 5.1 | 0.1 | 1.7 | 0.3 | 0.7 | 1.6 | |||||||||||
| Some Other Provider .............. | 18.3 | 0.5 | 2.6 | 2.5 | 0.2 | 7.2 | 0.1 | 1.5 | Q | 1.0 | 2.1 | |||||||||||
| See "Guide to the Tables" or "Glossary" for
further explanations of the terms used in this table. Both can be accessed
from the CBECS web site - http://www.eia.gov/consumption/commercial/. * Figures in this table do not include enclosed malls and strip malls. In the 1999 CBECS, malls represented 9.7 percent of total electricity consumption. (*)=Value rounds to zero in the units displayed. Q=Data withheld because fewer than 20 buildings were sampled for any cell, or because the Relative Standard Error (RSE) was greater than 50 percent for a cell in the "Total" column. |
||||||||||||||||||||||
| Notes: ● Due to rounding, data may not sum to totals.
● HVAC = Heating, Ventilation, and Air Conditioning. Source: Energy Information Administration, Office of Energy Markets and End Use, Form EIA-871A, C, and E of the 2003 Commercial Buildings Energy Consumption Survey. |
||||||||||||||||||||||