| Table E4. Electricity Consumption (Btu) Intensities by End Use for Non-Mall Buildings, 2003 | |||||||||||
| Electricity Energy Intensity (thousand Btu/square foot) | |||||||||||
| Total | Space Heat- ing |
Cool- ing |
Venti- lation |
Water Heat- ing |
Light- ing |
Cook- ing |
Refrig- eration |
Office Equip- ment |
Com- puters |
Other | |
| All Buildings* ........................ | 48.0 | 1.8 | 6.3 | 6.1 | 0.8 | 18.1 | 0.3 | 5.6 | 1.0 | 2.3 | 5.6 |
| Building Floorspace | |||||||||||
| (Square Feet) | |||||||||||
| 1,001 to 5,000 ......................... | 60.8 | 2.9 | 6.8 | 2.9 | 1.7 | 14.6 | 1.1 | 21.6 | 1.2 | 1.9 | 6.0 |
| 5,001 to 10,000 ....................... | 42.2 | 2.0 | 5.6 | 2.8 | 0.9 | 13.3 | 0.7 | 9.0 | 0.9 | 1.5 | 5.7 |
| 10,001 to 25,000 ..................... | 35.8 | 1.7 | 4.1 | 3.9 | 0.7 | 13.3 | 0.3 | 4.6 | 0.8 | 1.7 | 4.7 |
| 25,001 to 50,000 ..................... | 41.8 | 1.8 | 6.6 | 6.0 | 1.0 | 14.4 | 0.2 | 4.1 | 0.8 | 1.9 | 5.0 |
| 50,001 to 100,000 ................... | 44.8 | 1.8 | 6.4 | 7.2 | 0.8 | 17.5 | 0.3 | 3.3 | 0.7 | 2.0 | 5.0 |
| 100,001 to 200,000 ................. | 53.5 | 1.8 | 6.9 | 8.8 | 0.5 | 21.7 | 0.1 | 2.7 | Q | 3.5 | 6.2 |
| 200,001 to 500,000 ................. | 51.2 | 1.2 | 7.2 | 7.6 | 0.7 | 23.0 | 0.2 | 1.2 | 1.1 | 2.7 | 6.1 |
| Over 500,000 .......................... | 64.9 | 1.4 | 7.9 | 9.5 | 0.5 | 30.6 | 0.3 | 2.1 | 1.4 | 3.9 | 7.3 |
| Principal Building Activity | |||||||||||
| Education ................................ | 37.6 | 1.5 | 7.5 | 8.4 | 1.1 | 11.5 | 0.2 | 1.6 | 0.4 | 3.3 | 2.1 |
| Food Sales .............................. | 168.5 | 5.1 | 9.9 | 6.0 | Q | 37.2 | 1.9 | 96.1 | 1.6 | 1.5 | 8.1 |
| Food Service .......................... | 130.9 | 6.3 | 17.0 | 14.8 | 6.3 | 25.4 | 8.1 | 42.1 | 1.0 | 1.0 | 8.9 |
| Health Care ............................. | 78.3 | 1.9 | 10.6 | 13.3 | 0.8 | 33.1 | 0.2 | 2.6 | 1.2 | 3.2 | 11.3 |
| Inpatient ................................ | 93.7 | 1.6 | 13.0 | 20.0 | 1.1 | 40.1 | 0.4 | 2.0 | 1.1 | 3.6 | 10.9 |
| Outpatient ............................. | 55.0 | 2.3 | 7.0 | 3.3 | 0.3 | 22.6 | 0.1 | 3.5 | 1.3 | 2.6 | 12.0 |
| Lodging ................................... | 46.1 | 2.8 | 4.7 | 2.7 | 2.3 | 24.3 | 0.4 | 2.3 | Q | 1.2 | 4.7 |
| Retail (Other Than Mall)........... | 48.8 | 1.5 | 5.9 | 3.7 | 0.4 | 25.7 | 0.1 | 5.0 | 0.6 | 0.9 | 5.1 |
| Office ...................................... | 58.9 | 2.7 | 8.3 | 5.2 | 0.6 | 23.1 | 0.1 | 2.9 | 2.6 | 6.1 | 7.5 |
| Public Assembly ..................... | 42.6 | 1.3 | 8.9 | 15.9 | 0.1 | 7.0 | 0.1 | 2.2 | Q | 0.8 | 5.8 |
| Public Order and Safety ......... | 52.3 | 1.6 | 7.2 | 9.5 | 3.0 | 16.5 | 0.1 | 2.9 | 0.6 | 1.5 | 9.2 |
| Religious Worship ................... | 16.6 | 0.8 | 2.8 | 1.4 | 0.1 | 4.4 | 0.1 | 1.7 | 0.1 | 0.2 | 4.9 |
| Service ................................... | 37.5 | 1.4 | 3.8 | 6.1 | 0.1 | 15.8 | Q | 2.2 | 0.3 | 0.8 | 7.0 |
| Warehouse and Storage ........ | 25.9 | 0.5 | 1.4 | 2.2 | 0.2 | 14.0 | Q | 3.8 | 0.2 | 0.5 | 3.2 |
| Other ....................................... | 76.8 | 1.4 | 9.3 | 6.1 | 0.3 | 34.3 | Q | 6.0 | Q | 2.9 | 12.6 |
| Vacant .................................... | 8.3 | 0.5 | 0.8 | 0.5 | Q | 2.4 | Q | 0.2 | Q | 0.1 | 3.7 |
| Year Constructed | |||||||||||
| Before 1920 ............................ | 24.1 | 0.5 | 1.7 | 2.9 | Q | 9.2 | 0.3 | 4.5 | 0.6 | 0.9 | 3.2 |
| 1920 to 1945 ........................... | 31.5 | 0.6 | 2.4 | 4.5 | 0.3 | 13.5 | 0.2 | 3.9 | 0.4 | 1.2 | 4.5 |
| 1946 to 1959 ........................... | 33.7 | 1.2 | 3.8 | 5.0 | 0.7 | 12.8 | 0.3 | 3.8 | 0.6 | 1.6 | 4.1 |
| 1960 to 1969 ........................... | 40.6 | 1.4 | 5.3 | 6.2 | 0.7 | 14.1 | 0.2 | 4.9 | 0.8 | 2.3 | 4.8 |
| 1970 to 1979 ........................... | 54.2 | 2.5 | 6.8 | 7.0 | 1.0 | 20.9 | 0.4 | 5.5 | 1.2 | 2.6 | 6.3 |
| 1980 to 1989 ........................... | 61.7 | 2.8 | 9.0 | 6.5 | 1.2 | 23.3 | 0.4 | 6.5 | 1.5 | 3.6 | 7.1 |
| 1990 to 1999 ........................... | 57.1 | 2.0 | 8.2 | 7.3 | 1.0 | 20.4 | 0.5 | 7.0 | 1.4 | 2.9 | 6.4 |
| 2000 to 2003 ........................... | 55.3 | 1.9 | 8.4 | 6.0 | 0.8 | 22.0 | 0.5 | 7.1 | 0.7 | 1.7 | 6.1 |
| Census Region and Division | |||||||||||
| Northeast ................................ | 39.3 | 1.5 | 2.9 | 5.2 | 0.5 | 16.1 | 0.2 | 4.6 | 1.0 | 2.4 | 5.0 |
| New England ........................ | 36.7 | 1.6 | 2.0 | 4.1 | 0.7 | 14.2 | 0.3 | 6.5 | 0.7 | 2.1 | 4.4 |
| Middle Atlantic ....................... | 40.0 | 1.5 | 3.1 | 5.6 | 0.4 | 16.6 | 0.1 | 4.0 | 1.0 | 2.4 | 5.2 |
| Midwest .................................. | 44.1 | 2.6 | 3.1 | 6.1 | 0.6 | 17.2 | 0.3 | 5.3 | 0.9 | 2.1 | 5.7 |
| East North Central ................. | 46.0 | 2.4 | 3.0 | 6.8 | 0.6 | 18.3 | 0.3 | 5.2 | 1.0 | 2.3 | 6.0 |
| West North Central ............... | 40.0 | 3.0 | 3.4 | 4.8 | 0.8 | 14.8 | 0.2 | 5.5 | 0.7 | 1.6 | 5.1 |
| South ...................................... | 56.1 | 1.4 | 10.6 | 6.7 | 1.2 | 19.7 | 0.5 | 6.8 | 0.8 | 2.4 | 5.9 |
| South Atlantic ....................... | 59.3 | 1.6 | 10.2 | 7.0 | 1.6 | 21.4 | 0.6 | 7.2 | 0.9 | 2.9 | 5.9 |
| East South Central ................ | 53.0 | 1.8 | 7.1 | 6.9 | 0.9 | 19.6 | Q | 7.5 | 0.6 | 1.6 | 6.6 |
| West South Central ............... | 52.3 | 1.0 | 12.8 | 6.2 | 0.8 | 17.2 | 0.5 | 5.8 | 0.7 | 1.9 | 5.5 |
| West ....................................... | 47.1 | 1.6 | 6.0 | 5.6 | 0.6 | 18.2 | 0.3 | 4.8 | 1.7 | 2.5 | 5.8 |
| Mountain ............................... | 52.5 | 2.0 | 7.0 | 6.3 | 0.6 | 21.6 | Q | 5.0 | Q | 2.3 | 6.1 |
| Pacific ................................... | 44.4 | 1.5 | 5.5 | 5.2 | 0.7 | 16.5 | 0.3 | 4.7 | Q | 2.6 | 5.7 |
| Climate Zone: 30-Year Average | |||||||||||
| Under 2,000 CDD and -- | |||||||||||
| More than 7,000 HDD ............ | 39.3 | 2.2 | 2.1 | 5.8 | 0.5 | 15.1 | 0.3 | 5.6 | 0.8 | 1.7 | 5.1 |
| 5,500-7,000 HDD .................. | 44.7 | 2.6 | 3.2 | 5.8 | 0.6 | 18.1 | 0.3 | 5.2 | 1.0 | 2.3 | 5.7 |
| 4,000-5,499 HDD .................. | 49.9 | 2.0 | 5.1 | 6.1 | 0.7 | 20.2 | 0.3 | 5.4 | 1.6 | 2.7 | 5.8 |
| Fewer than 4,000 HDD ......... | 49.3 | 1.1 | 7.4 | 6.2 | 1.1 | 18.1 | 0.4 | 6.1 | 0.9 | 2.2 | 5.8 |
| 2,000 CDD or More and -- | |||||||||||
| Fewer than 4,000 HDD ......... | 59.2 | 1.0 | 16.1 | 6.7 | 1.2 | 18.5 | 0.5 | 5.7 | 0.8 | 2.9 | 5.7 |
| Number of Floors | |||||||||||
| One ......................................... | 45.7 | 2.0 | 6.2 | 4.4 | 0.9 | 15.4 | 0.5 | 9.2 | 0.7 | 1.4 | 5.0 |
| Two ........................................ | 43.1 | 1.6 | 5.5 | 6.1 | 1.0 | 15.9 | 0.3 | 4.4 | 1.1 | 2.0 | 5.3 |
| Three ...................................... | 38.7 | 1.8 | 4.4 | 5.4 | 0.6 | 15.3 | 0.2 | 2.9 | 1.0 | 2.2 | 5.1 |
| Four to Nine ............................ | 59.1 | 1.6 | 8.0 | 9.9 | 0.6 | 23.9 | 0.2 | 2.5 | 1.2 | 4.0 | 7.1 |
| Ten or More ............................ | 66.1 | 2.1 | 8.4 | 7.6 | 0.7 | 30.7 | 0.3 | 1.5 | 1.9 | 5.1 | 7.7 |
| Elevators and Escalators | |||||||||||
| (more than one may apply) | |||||||||||
| Any Elevators ......................... | 58.0 | 1.9 | 7.9 | 9.0 | 0.7 | 23.7 | 0.2 | 2.2 | 1.6 | 3.9 | 6.9 |
| Number of Elevators................ | |||||||||||
| One ....................................... | 43.7 | 1.7 | 5.8 | 7.5 | 0.7 | 16.5 | 0.1 | 2.5 | 0.9 | 2.7 | 5.2 |
| Two to Five ........................... | 57.8 | 2.2 | 7.8 | 8.8 | 0.7 | 23.1 | 0.2 | 2.1 | 1.8 | 4.2 | 6.9 |
| Six or More ........................... | 76.8 | 1.7 | 10.8 | 11.2 | 0.7 | 34.1 | 0.3 | 1.9 | 2.0 | 5.0 | 9.1 |
| Any Escalators ....................... | 82.2 | 2.1 | 13.4 | 12.7 | 0.7 | 33.9 | Q | 1.8 | Q | 4.8 | 9.3 |
| Number of Workers (main shift) | |||||||||||
| Fewer than 5 .......................... | 26.4 | 1.3 | 2.8 | 2.0 | 0.5 | 8.5 | 0.2 | 6.6 | 0.2 | 0.4 | 4.0 |
| 5 to 9 ....................................... | 40.4 | 2.0 | 5.0 | 3.5 | 0.9 | 12.6 | 0.6 | 9.1 | 0.7 | 1.0 | 5.0 |
| 10 to 19 ................................... | 38.8 | 2.2 | 5.1 | 3.9 | 1.0 | 13.2 | 0.7 | 6.7 | 0.6 | 1.1 | 4.4 |
| 20 to 49 ................................... | 47.8 | 1.6 | 6.5 | 6.3 | 0.9 | 17.5 | 0.4 | 6.1 | 1.3 | 1.9 | 5.4 |
| 50 to 99 ................................... | 50.8 | 2.0 | 6.9 | 8.4 | 0.9 | 19.1 | 0.3 | 4.7 | 1.0 | 2.4 | 5.2 |
| 100 to 249 ............................... | 66.9 | 2.3 | 9.8 | 9.8 | 1.2 | 27.3 | 0.3 | 4.0 | 1.3 | 3.7 | 7.2 |
| 250 or More ............................ | 76.3 | 1.9 | 10.0 | 10.5 | 0.7 | 32.9 | 0.2 | 2.3 | 2.1 | 6.6 | 9.0 |
| Weekly Operating Hours | |||||||||||
| Fewer than 40 ........................ | 15.3 | 0.9 | 2.9 | 1.2 | 0.2 | 3.7 | 0.2 | 1.9 | 0.1 | 0.4 | 3.7 |
| 40 to 48 ................................... | 34.3 | 1.9 | 5.7 | 3.6 | 0.5 | 11.5 | 0.1 | 2.9 | 0.9 | 2.2 | 5.2 |
| 49 to 60 ................................... | 38.1 | 1.5 | 5.3 | 4.5 | 0.5 | 14.6 | 0.1 | 3.2 | 1.0 | 2.2 | 5.3 |
| 61 to 84 ................................... | 48.2 | 1.8 | 6.0 | 6.5 | 0.8 | 17.9 | 0.4 | 6.2 | 0.9 | 2.3 | 5.3 |
| 85 to 167 ................................. | 75.4 | 2.3 | 7.7 | 11.1 | 1.3 | 24.0 | 1.4 | 17.2 | 0.8 | 3.1 | 6.3 |
| Open Continuously ................. | 72.3 | 2.3 | 9.0 | 9.3 | 1.6 | 31.7 | 0.3 | 5.9 | 1.8 | 3.2 | 7.2 |
| Ownership and Occupancy | |||||||||||
| Nongovernment Owned.......... | 47.9 | 1.9 | 5.8 | 4.7 | 0.8 | 18.7 | 0.4 | 6.6 | 1.1 | 2.1 | 5.8 |
| Owner Occupied .................. | 46.3 | 1.6 | 5.8 | 4.9 | 0.7 | 18.1 | 0.2 | 5.7 | 1.2 | 2.2 | 5.9 |
| Nonowner Occupied ............ | 51.8 | 2.2 | 6.2 | 4.6 | 0.9 | 20.3 | 0.6 | 7.9 | 1.1 | 2.2 | 5.8 |
| Unoccupied ........................... | 6.4 | Q | Q | 0.2 | Q | 1.7 | (*) | Q | Q | Q | 3.2 |
| Government Owned ............... | 48.2 | 1.6 | 7.7 | 10.5 | 0.9 | 16.1 | 0.2 | 2.3 | 0.7 | 3.0 | 5.3 |
| Federal .................................. | 67.1 | 0.9 | 6.5 | 12.2 | 0.2 | 32.5 | 0.1 | 1.6 | 0.8 | 2.8 | 9.5 |
| State ..................................... | 53.9 | 0.8 | 6.7 | 14.1 | 0.8 | 16.3 | 0.1 | 2.5 | 0.8 | 5.4 | 6.4 |
| Local ..................................... | 42.0 | 2.0 | 8.3 | 8.7 | 1.1 | 12.6 | 0.3 | 2.4 | 0.5 | 2.2 | 3.9 |
| Vacancy Status | |||||||||||
| Completely Vacant .................. | 6.2 | Q | Q | 0.2 | Q | 1.7 | Q | Q | Q | Q | 3.1 |
| Mostly Vacant ......................... | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q |
| Partially Vacant ....................... | 47.1 | 2.0 | 6.2 | 5.6 | 0.6 | 19.6 | 0.2 | 2.5 | 1.0 | 3.4 | 6.0 |
| Not At All Vacant .................... | 49.7 | 1.8 | 6.5 | 6.4 | 0.9 | 18.2 | 0.4 | 6.6 | 1.0 | 2.2 | 5.6 |
| Number of Establishments | |||||||||||
| One ......................................... | 48.2 | 1.8 | 6.1 | 6.1 | 1.0 | 17.8 | 0.4 | 6.5 | 0.9 | 2.0 | 5.5 |
| 2 to 5 ....................................... | 46.0 | 1.5 | 6.1 | 5.9 | 0.5 | 18.2 | 0.2 | 4.5 | 1.1 | 2.2 | 5.8 |
| 6 to 10 ..................................... | 58.9 | 2.7 | 7.4 | 7.1 | 0.8 | 22.1 | 0.1 | 2.4 | 1.4 | 8.2 | 6.7 |
| 11 to 20 ................................... | 50.1 | 2.8 | 7.4 | 6.3 | 0.5 | 19.1 | 0.1 | Q | 1.0 | 3.3 | 6.8 |
| More than 20 ........................... | 66.8 | 2.0 | 11.0 | 8.4 | 0.6 | 27.4 | 0.1 | 1.8 | 2.0 | 5.7 | 7.7 |
| Currently Unoccupied ............. | 6.2 | Q | Q | 0.2 | Q | 1.7 | Q | Q | Q | Q | 3.1 |
| Predominant Exterior | |||||||||||
| Wall Material | |||||||||||
| Brick, Stone or Stucco ............ | 46.7 | 1.8 | 6.4 | 6.4 | 1.0 | 16.4 | 0.4 | 5.6 | 0.9 | 2.3 | 5.5 |
| Concrete (Block or Poured) .... | 49.3 | 1.7 | 6.7 | 5.8 | 0.8 | 18.8 | 0.3 | 6.7 | 1.2 | 1.7 | 5.6 |
| Concrete Panels ..................... | 62.6 | 1.4 | 7.8 | 7.3 | 0.6 | 29.0 | 0.2 | 3.4 | 1.6 | 4.5 | 6.7 |
| Siding or Shingles ................... | 37.7 | 2.3 | 4.2 | 3.4 | 0.9 | 12.3 | 0.5 | 7.2 | 0.9 | 1.4 | 4.5 |
| Metal Panels ............................ | 40.3 | 1.6 | 3.3 | 4.8 | 0.5 | 16.3 | Q | 6.0 | 0.5 | 1.5 | 5.7 |
| Window Glass ........................ | 65.2 | 3.0 | 10.4 | 7.2 | 1.0 | 24.7 | 0.1 | 2.0 | 1.9 | 6.2 | 8.8 |
| Other ....................................... | 56.8 | 3.1 | 8.6 | 5.9 | 0.3 | 22.9 | 0.7 | 3.7 | 1.3 | 3.9 | 6.4 |
| No One Major Type ................. | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q |
| Predominant Roof Material | |||||||||||
| Built-Up ................................... | 50.1 | 1.5 | 6.9 | 6.5 | 0.8 | 19.5 | 0.4 | 5.2 | 1.1 | 2.7 | 5.6 |
| Shingles (Not Wood) ............... | 41.8 | 1.9 | 5.1 | 4.2 | 1.3 | 13.6 | 0.4 | 8.0 | 0.9 | 1.5 | 5.1 |
| Metal Surfacing ....................... | 34.9 | 1.6 | 4.2 | 4.2 | 0.6 | 13.4 | Q | 4.1 | 0.4 | 1.1 | 4.9 |
| Synthetic or Rubber ................ | 60.5 | 2.5 | 7.9 | 8.6 | 0.8 | 22.4 | 0.4 | 6.2 | 1.5 | 3.6 | 6.7 |
| Slate or Tile ............................. | 42.5 | 1.7 | 6.6 | 4.4 | 0.7 | 14.1 | 0.6 | 6.9 | 0.8 | 1.8 | 5.1 |
| Wooden Materials ................... | 41.6 | 2.5 | 6.3 | 4.4 | 1.0 | 16.1 | (*) | 4.7 | 0.7 | 1.2 | 4.5 |
| Concrete ................................. | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q |
| Other ....................................... | 69.7 | 0.7 | 9.9 | 5.5 | Q | 37.7 | Q | 5.6 | 0.4 | 2.0 | 6.9 |
| No One Major Type ................. | 35.5 | Q | 4.7 | 6.6 | Q | 10.8 | Q | Q | 0.7 | Q | 4.6 |
| Renovations in Buildings | |||||||||||
| Constructed Before 1980 | |||||||||||
| (more than one may apply) | |||||||||||
| Any Type of Renovation | |||||||||||
| Since 1980 ............................. | 44.2 | 1.7 | 4.8 | 6.4 | 0.8 | 16.9 | 0.3 | 5.0 | 0.9 | 2.4 | 5.1 |
| Addition or Annex ................ | 48.1 | 1.9 | 5.3 | 8.4 | 0.8 | 18.5 | 0.4 | 4.7 | 0.6 | 2.1 | 5.4 |
| Reduction In Floorspace ...... | 51.8 | 1.7 | 5.2 | 8.9 | 0.9 | 22.0 | 0.2 | 2.3 | 0.9 | 3.0 | 6.7 |
| Cosmetic Improvements ....... | 46.2 | 1.8 | 4.9 | 6.5 | 0.8 | 17.7 | 0.3 | 5.4 | 0.9 | 2.6 | 5.2 |
| Wall or Roof Replacement ... | 43.0 | 1.4 | 4.7 | 6.6 | 0.8 | 17.3 | 0.3 | 3.4 | 0.9 | 2.7 | 4.9 |
| Interior Wall | |||||||||||
| Re-Configuration ................ | 47.2 | 1.7 | 5.1 | 7.2 | 0.6 | 19.1 | 0.2 | 3.8 | 0.9 | 2.8 | 5.7 |
| HVAC Equipment Upgrade.... | 49.0 | 1.9 | 5.5 | 7.5 | 0.8 | 19.1 | 0.3 | 4.2 | 1.1 | 3.0 | 5.6 |
| Lighting Upgrade .................. | 46.5 | 1.7 | 4.8 | 7.3 | 0.7 | 17.9 | 0.2 | 4.7 | 1.0 | 2.7 | 5.4 |
| Window Replacement .......... | 39.9 | 1.5 | 3.6 | 5.9 | 0.7 | 15.9 | 0.2 | 4.1 | 0.7 | 2.6 | 4.7 |
| Plumbing System Upgrade ... | 43.9 | 1.4 | 4.5 | 7.0 | 0.7 | 18.1 | 0.2 | 3.5 | 0.7 | 2.6 | 5.1 |
| Insulation Upgrade ............... | 43.4 | 1.4 | 4.9 | 7.5 | 0.6 | 16.1 | 0.3 | 3.8 | 0.8 | 2.7 | 5.3 |
| Other Renovation ................. | 30.8 | 1.4 | 2.0 | 4.3 | Q | 13.8 | 0.3 | 3.4 | 0.3 | 1.0 | 3.7 |
| No Renovations Since 1980.... | 35.7 | 1.2 | 4.3 | 4.8 | 0.5 | 13.6 | 0.2 | 4.3 | 0.7 | 1.4 | 4.7 |
| Building Newer than 1980 ...... | 58.5 | 2.3 | 8.5 | 6.7 | 1.0 | 21.8 | 0.5 | 6.8 | 1.3 | 2.9 | 6.6 |
| Energy Sources (more than | |||||||||||
| one may apply) | |||||||||||
| Electricity ................................ | 48.0 | 1.8 | 6.3 | 6.1 | 0.8 | 18.1 | 0.3 | 5.6 | 1.0 | 2.3 | 5.6 |
| Natural Gas ............................. | 49.7 | 1.4 | 6.2 | 6.8 | 0.7 | 19.4 | 0.4 | 5.5 | 1.0 | 2.5 | 5.9 |
| Fuel Oil .................................... | 56.4 | 1.9 | 7.2 | 8.0 | 0.8 | 23.7 | 0.2 | 2.8 | 1.6 | 3.4 | 6.7 |
| District Heat ............................ | 61.5 | 0.5 | 4.4 | 12.8 | 0.6 | 26.9 | 0.1 | 2.2 | 0.8 | 5.4 | 7.7 |
| District Chilled Water ............... | 67.4 | 0.7 | 5.6 | 17.2 | 0.8 | 23.9 | 0.2 | 2.6 | 1.0 | 7.2 | 8.2 |
| Propane .................................. | 47.9 | 1.2 | 5.1 | 5.7 | 0.8 | 19.9 | 0.3 | 7.2 | 0.7 | 1.3 | 5.7 |
| Other ....................................... | 56.0 | 1.4 | 5.5 | 10.1 | 0.5 | 21.9 | 0.2 | 4.6 | Q | 2.8 | 7.3 |
| Space-Heating Energy Sources | |||||||||||
| Electricity ................................ | 54.4 | 4.0 | 7.9 | 5.4 | 1.3 | 20.0 | 0.4 | 5.7 | 1.3 | 2.4 | 5.9 |
| Electricity Main ...................... | 56.7 | 5.7 | 9.4 | 4.3 | 1.8 | 19.0 | 0.5 | 6.9 | 1.3 | 2.3 | 5.5 |
| Electricity Secondary ............ | 51.5 | 1.8 | 5.9 | 6.9 | 0.7 | 21.3 | 0.4 | 4.2 | 1.2 | 2.6 | 6.4 |
| Other Excluding Electricity ...... | 44.2 | (*) | 4.8 | 7.0 | 0.4 | 17.3 | 0.3 | 5.4 | 0.8 | 2.4 | 5.6 |
| Buildings without Heating ....... | 28.1 | (*) | 6.1 | 2.3 | 0.3 | 8.9 | 0.4 | 5.8 | 0.3 | 0.6 | 3.5 |
| Primary Space-Heating | |||||||||||
| Energy Source | |||||||||||
| Electricity ................................ | 56.7 | 5.7 | 9.4 | 4.3 | 1.8 | 19.0 | 0.5 | 6.9 | 1.3 | 2.3 | 5.5 |
| Natural Gas ............................. | 47.5 | 0.6 | 5.8 | 6.6 | 0.5 | 18.8 | 0.3 | 5.4 | 1.0 | 2.3 | 6.0 |
| Fuel Oil .................................... | 20.1 | 0.2 | 1.5 | 3.4 | 0.3 | 7.5 | 0.1 | 3.3 | 0.3 | 1.0 | 2.4 |
| District Heat ............................ | 63.1 | 0.4 | 4.2 | 13.3 | 0.6 | 27.6 | 0.1 | 2.2 | 0.9 | 5.6 | 8.1 |
| Propane .................................. | 35.8 | 0.5 | 3.8 | 4.4 | 0.5 | 9.3 | Q | 9.9 | Q | Q | 5.0 |
| Other ....................................... | 43.1 | 0.5 | 2.8 | 5.0 | 0.4 | 20.5 | 0.1 | 6.1 | 0.5 | Q | 6.0 |
| Cooling Energy Source | |||||||||||
| Electricity ................................ | 51.1 | 2.0 | 7.3 | 6.0 | 0.9 | 19.0 | 0.4 | 6.2 | 1.1 | 2.3 | 5.8 |
| Other Excluding Electricity ...... | 59.6 | Q | (*) | 16.1 | 0.7 | 23.9 | 0.2 | 2.3 | 1.0 | 7.7 | 7.3 |
| Buildings without Cooling ........ | 16.2 | 0.6 | (*) | 2.4 | 0.1 | 7.5 | 0.1 | 2.1 | 0.1 | 0.3 | 3.2 |
| Water-Heating Energy Source | |||||||||||
| Electricity ................................ | 50.0 | 2.6 | 7.1 | 5.2 | 1.9 | 17.7 | 0.3 | 5.7 | 1.2 | 2.4 | 5.8 |
| Other Excluding Electricity ...... | 52.4 | 1.3 | 6.4 | 7.9 | (*) | 20.5 | 0.4 | 6.2 | 1.0 | 2.7 | 6.0 |
| Bldgs without Water Heating .. | 21.1 | 0.6 | 2.3 | 2.1 | (*) | 9.1 | Q | 2.6 | 0.2 | 0.4 | 3.6 |
| Cooking Energy Source | |||||||||||
| Electricity ................................ | 64.4 | 2.8 | 8.9 | 9.5 | 1.6 | 22.3 | 1.7 | 7.8 | 1.1 | 2.8 | 6.0 |
| Other Excluding Electricity ...... | 58.3 | 1.6 | 8.4 | 8.5 | 0.9 | 21.2 | (*) | 8.9 | 1.0 | 2.0 | 5.7 |
| Buildings without Cooking ....... | 40.4 | 1.5 | 5.0 | 4.4 | 0.6 | 16.0 | (*) | 4.1 | 1.0 | 2.3 | 5.5 |
| Energy End Uses (more than | |||||||||||
| one may apply) | |||||||||||
| Buildings with Space Heating . | 49.1 | 1.9 | 6.3 | 6.3 | 0.9 | 18.6 | 0.3 | 5.6 | 1.0 | 2.4 | 5.8 |
| Buildings with Cooling ............. | 51.5 | 2.0 | 7.0 | 6.5 | 0.9 | 19.2 | 0.4 | 6.0 | 1.1 | 2.6 | 5.9 |
| Buildings with Water Heating .. | 51.2 | 2.0 | 6.8 | 6.5 | 0.9 | 19.1 | 0.4 | 6.0 | 1.1 | 2.6 | 5.9 |
| Buildings with Cooking ............ | 61.9 | 2.3 | 8.7 | 9.1 | 1.3 | 21.9 | 1.0 | 8.3 | 1.0 | 2.5 | 5.9 |
| Buildings with Manufacturing . | 45.0 | 1.3 | 3.0 | 5.4 | Q | 20.5 | Q | 3.2 | 0.6 | 2.1 | 7.8 |
| Buildings with Electricity | |||||||||||
| Generation ............................. | 69.4 | 2.4 | 9.1 | 10.1 | 1.0 | 28.6 | 0.3 | 3.3 | 2.2 | 4.4 | 8.0 |
| Percent of Floorspace Heated | |||||||||||
| Not Heated .............................. | 28.1 | (*) | 6.1 | 2.3 | 0.3 | 8.9 | 0.4 | 5.8 | 0.3 | 0.6 | 3.5 |
| 1 to 50 ..................................... | 27.4 | 0.8 | 2.0 | 2.7 | 0.6 | 10.1 | Q | 5.7 | Q | 0.6 | 3.6 |
| 51 to 99 ................................... | 48.7 | 1.7 | 6.1 | 6.0 | 0.8 | 18.7 | 0.3 | 6.7 | 0.8 | 1.9 | 5.6 |
| 100 .......................................... | 52.4 | 2.1 | 7.0 | 6.9 | 0.9 | 19.8 | 0.4 | 5.4 | 1.1 | 2.8 | 6.1 |
| Percent of Floorspace Cooled | |||||||||||
| Not Cooled .............................. | 16.2 | 0.6 | (*) | 2.4 | 0.1 | 7.5 | 0.1 | 2.1 | 0.1 | 0.3 | 3.2 |
| 1 to 50 ..................................... | 26.7 | 0.9 | 1.4 | 3.4 | 0.4 | 11.8 | Q | 3.9 | 0.3 | 0.8 | 3.8 |
| 51 to 99 ................................... | 56.5 | 2.2 | 7.0 | 7.4 | 0.8 | 20.7 | 0.4 | 7.9 | 1.0 | 2.9 | 6.2 |
| 100 .......................................... | 64.3 | 2.5 | 10.4 | 7.9 | 1.3 | 23.1 | 0.5 | 6.4 | 1.7 | 3.6 | 7.0 |
| Percent Lit When Open | |||||||||||
| Zero ........................................ | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q |
| 1 to 50 ..................................... | 22.0 | 1.2 | 3.1 | 2.8 | 0.5 | 6.2 | 0.2 | 2.8 | Q | 0.6 | 3.9 |
| 51 to 99 ................................... | 48.9 | 1.9 | 6.3 | 6.8 | 0.9 | 18.0 | 0.3 | 4.8 | 1.1 | 3.1 | 5.7 |
| 100 .......................................... | 58.0 | 2.1 | 7.6 | 7.0 | 0.9 | 22.8 | 0.5 | 7.2 | 1.1 | 2.6 | 6.3 |
| Building Never Open/ | |||||||||||
| Electricity Not Used ................ | 7.1 | Q | 0.7 | 0.2 | Q | 2.1 | Q | 0.3 | Q | Q | 3.3 |
| Percent Lit When Closed | |||||||||||
| Zero ........................................ | 31.2 | 1.2 | 4.1 | 4.0 | 0.4 | 10.0 | 0.2 | 4.2 | 0.5 | 1.7 | 4.8 |
| 1 to 50 ..................................... | 45.5 | 1.9 | 6.3 | 5.8 | 0.7 | 15.7 | 0.4 | 5.8 | 1.0 | 2.3 | 5.5 |
| 51 to 100 ................................. | 74.0 | 2.6 | 7.5 | 6.8 | 1.1 | 35.6 | 0.6 | 11.5 | 0.8 | 2.2 | 5.3 |
| Building Never Closed/ | |||||||||||
| Electricity Not Used ................ | 72.3 | 2.3 | 9.0 | 9.3 | 1.6 | 31.7 | 0.3 | 5.9 | 1.8 | 3.2 | 7.2 |
| Heating Equipment (more | |||||||||||
| than one may apply) | |||||||||||
| Heat Pumps ............................. | 59.3 | 3.1 | 9.9 | 6.0 | 1.5 | 22.8 | 0.4 | 5.2 | 1.3 | 2.8 | 6.2 |
| Packaged Heat Pumps .......... | 66.0 | 3.3 | 11.2 | 6.1 | 1.4 | 25.9 | 0.4 | 6.0 | 1.6 | 3.2 | 6.9 |
| Split-System Heat Pumps ...... | 52.6 | 2.3 | 9.1 | 7.0 | 1.4 | 19.6 | Q | 4.3 | 0.8 | 1.8 | 5.8 |
| Individual Room Heat Pumps . | 55.1 | 3.1 | 9.4 | 6.2 | 1.9 | 22.3 | 0.3 | 2.7 | 0.8 | 2.9 | 5.3 |
| Furnaces ................................ | 38.8 | 1.8 | 4.0 | 4.3 | 0.7 | 14.6 | 0.3 | 6.3 | 0.7 | 1.4 | 4.8 |
| Individual Space Heaters ........ | 44.9 | 2.9 | 4.8 | 5.1 | 0.9 | 18.0 | 0.2 | 4.9 | 0.8 | 2.0 | 5.2 |
| District Heat ............................ | 61.4 | 0.5 | 4.2 | 12.8 | 0.6 | 26.9 | 0.1 | 2.1 | 0.9 | 5.5 | 7.8 |
| Boilers ..................................... | 49.4 | 1.3 | 6.2 | 8.2 | 0.6 | 19.9 | 0.2 | 2.9 | 1.2 | 2.7 | 6.2 |
| Packaged Heating Units .......... | 58.7 | 2.8 | 8.7 | 6.6 | 1.2 | 21.3 | 0.6 | 7.4 | 1.4 | 2.6 | 6.2 |
| Other ....................................... | 51.9 | 3.1 | 6.4 | 6.2 | 1.0 | 19.8 | 0.2 | 5.7 | 0.8 | 2.5 | 6.3 |
| Cooling Equipment (more | |||||||||||
| than one may apply) | |||||||||||
| Residential-Type Central | |||||||||||
| Air Conditioners ..................... | 41.3 | 1.7 | 5.3 | 6.1 | 1.0 | 14.3 | 0.4 | 5.3 | 0.7 | 1.4 | 5.1 |
| Heat Pumps ............................. | 60.5 | 2.9 | 10.1 | 6.0 | 1.5 | 23.1 | 0.4 | 6.0 | 1.3 | 2.8 | 6.4 |
| Packaged Heat Pumps .......... | 66.3 | 3.3 | 10.9 | 5.8 | 1.4 | 26.2 | 0.4 | 6.6 | 1.6 | 3.2 | 7.0 |
| Split-System Heat Pumps ...... | 53.5 | 2.1 | 9.4 | 7.2 | 1.4 | 19.2 | Q | 5.0 | 0.8 | 1.9 | 6.0 |
| Individual Room Heat Pumps . | 58.3 | 2.9 | 10.3 | 6.6 | 1.7 | 23.3 | 0.3 | 3.7 | 0.9 | 2.9 | 5.8 |
| Individual Air Conditioners ...... | 38.1 | 1.6 | 5.0 | 5.0 | 1.1 | 15.6 | 0.2 | 3.5 | 0.5 | 1.4 | 4.2 |
| District Chilled Water ............... | 67.4 | 0.7 | 5.6 | 17.2 | 0.8 | 23.9 | 0.2 | 2.6 | 1.0 | 7.2 | 8.2 |
| Central Chillers ........................ | 71.9 | 1.9 | 10.5 | 12.0 | 0.9 | 29.1 | 0.3 | 2.3 | 2.0 | 4.3 | 8.5 |
| Packaged Air Conditioning | |||||||||||
| Units ....................................... | 52.7 | 2.1 | 7.2 | 6.0 | 0.9 | 19.9 | 0.5 | 6.8 | 1.0 | 2.4 | 5.9 |
| Swamp Coolers ...................... | 48.1 | 1.3 | 5.5 | 5.8 | 1.4 | 18.1 | 0.6 | 7.7 | 0.5 | 1.4 | 5.8 |
| Other ....................................... | 61.3 | 2.1 | 9.3 | 8.5 | 0.4 | 23.2 | 0.2 | Q | 1.1 | 2.9 | 6.4 |
| Main Equipment Replaced Since | |||||||||||
| 1990 (more than one may apply) | |||||||||||
| Heating .................................... | 43.7 | 2.2 | 5.5 | 5.2 | 1.0 | 15.7 | 0.4 | 5.1 | 1.0 | 2.2 | 5.4 |
| Cooling .................................... | 46.5 | 2.0 | 5.9 | 5.7 | 0.9 | 17.3 | 0.3 | 5.2 | 1.1 | 2.6 | 5.4 |
| Water Heating Equipment | |||||||||||
| Centralized System ................. | 50.8 | 2.0 | 6.3 | 6.6 | 0.9 | 18.2 | 0.5 | 7.2 | 1.0 | 2.3 | 5.9 |
| Distributed System .................. | 41.8 | 1.8 | 6.5 | 4.7 | 0.8 | 15.5 | 0.3 | 4.5 | 0.8 | 2.0 | 5.0 |
| Combination of Centralized | |||||||||||
| and Distributed System .......... | 63.4 | 2.1 | 8.5 | 8.6 | 1.1 | 26.4 | 0.3 | 3.3 | 1.8 | 4.2 | 6.9 |
| Lighting Equipment Types | |||||||||||
| (more than one may apply) | |||||||||||
| Incandescent .......................... | 52.1 | 1.9 | 6.7 | 6.7 | 0.9 | 20.9 | 0.4 | 5.0 | 1.2 | 2.7 | 5.8 |
| Standard Fluorescent ............. | 49.4 | 1.9 | 6.5 | 6.3 | 0.8 | 18.5 | 0.4 | 5.8 | 1.1 | 2.5 | 5.8 |
| Compact Fluorescent .............. | 60.4 | 2.2 | 8.0 | 8.6 | 1.0 | 23.6 | 0.4 | 5.0 | 1.5 | 3.2 | 6.9 |
| High Intensity Discharge ......... | 54.6 | 1.8 | 6.4 | 8.2 | 0.8 | 22.9 | 0.3 | 4.0 | 1.1 | 2.9 | 6.3 |
| Halogen ................................... | 60.4 | 2.3 | 7.4 | 7.8 | 1.0 | 25.6 | 0.4 | 5.3 | 1.2 | 2.8 | 6.4 |
| Other ....................................... | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q | Q |
| Refrigeration Equipment | |||||||||||
| (more than one may apply) | |||||||||||
| Any Refrigeration.................... | 52.3 | 2.0 | 6.8 | 6.6 | 0.9 | 19.5 | 0.4 | 6.7 | 1.1 | 2.6 | 5.8 |
| Commercial Refrigeration ...... | 66.8 | 2.3 | 8.9 | 8.8 | 1.2 | 24.3 | 0.8 | 10.6 | 1.0 | 2.6 | 6.3 |
| Walk-In Units ....................... | 73.5 | 2.4 | 9.7 | 9.8 | 1.3 | 26.6 | 1.0 | 12.3 | 1.1 | 2.8 | 6.6 |
| Cases or Cabinets .............. | 70.5 | 2.4 | 9.4 | 9.1 | 1.2 | 25.6 | 0.9 | 11.7 | 1.1 | 2.6 | 6.6 |
| Residential-Type Units .......... | 45.5 | 1.8 | 6.1 | 6.1 | 0.8 | 17.5 | 0.2 | 4.1 | 0.9 | 2.5 | 5.5 |
| Vending Machines ................ | 56.2 | 1.9 | 7.4 | 7.8 | 0.9 | 22.2 | 0.3 | 5.2 | 1.3 | 3.1 | 6.2 |
| No Refrigeration ...................... | 25.7 | 1.1 | 3.7 | 3.3 | 0.4 | 10.9 | Q | (*) | 0.4 | 1.1 | 4.8 |
| Office Equipment (more | |||||||||||
| than one may apply) | |||||||||||
| Computers .............................. | 51.0 | 1.9 | 6.8 | 6.6 | 0.9 | 19.4 | 0.3 | 5.4 | 1.1 | 2.7 | 5.9 |
| With Flat Screen Monitors ..... | 60.1 | 2.1 | 8.1 | 8.5 | 0.8 | 23.2 | 0.3 | 4.2 | 1.7 | 4.1 | 7.1 |
| Dedicated Servers .................. | 56.0 | 2.0 | 7.5 | 7.7 | 0.8 | 21.9 | 0.2 | 4.5 | 1.6 | 3.4 | 6.3 |
| Laser Printers ......................... | 47.0 | 2.0 | 6.3 | 6.0 | 0.8 | 17.2 | 0.3 | 5.5 | 1.2 | 2.3 | 5.4 |
| Inkjet Printers .......................... | 56.5 | 1.9 | 7.8 | 7.5 | 0.9 | 22.3 | 0.3 | 4.9 | 1.2 | 3.2 | 6.6 |
| FAX Machines ........................ | 51.6 | 1.9 | 6.9 | 6.7 | 0.9 | 19.8 | 0.3 | 5.3 | 1.2 | 2.7 | 5.9 |
| Photocopiers ........................... | 51.0 | 1.8 | 6.9 | 7.1 | 0.7 | 20.1 | 0.2 | 4.0 | 1.3 | 2.9 | 6.0 |
| Number of Computers | |||||||||||
| None ....................................... | 25.9 | 1.0 | 2.6 | 1.9 | 0.6 | 8.5 | 0.4 | 7.2 | 0.1 | N | 3.7 |
| 1 to 4 ....................................... | 42.2 | 2.1 | 4.7 | 3.6 | 1.1 | 13.4 | 0.8 | 10.7 | 0.4 | 0.4 | 4.8 |
| 5 to 9 ....................................... | 38.1 | 2.0 | 5.4 | 3.8 | 0.6 | 14.1 | 0.3 | 5.6 | 0.6 | 0.9 | 4.8 |
| 10 to 19 ................................... | 43.1 | 1.6 | 5.9 | 5.0 | 0.7 | 16.3 | 0.2 | 6.0 | 0.7 | 1.3 | 5.3 |
| 20 to 49 ................................... | 55.1 | 1.7 | 7.2 | 7.6 | 0.9 | 21.7 | Q | 5.1 | Q | 2.2 | 6.7 |
| 50 to 99 ................................... | 48.1 | 1.7 | 7.0 | 7.1 | 0.9 | 20.1 | 0.1 | 2.1 | 1.1 | 2.7 | 5.4 |
| 100 to 249 ............................... | 55.0 | 2.3 | 8.0 | 9.2 | 0.9 | 21.2 | 0.1 | 2.4 | 1.0 | 3.7 | 6.1 |
| 250 or More ............................ | 72.4 | 2.0 | 9.7 | 11.0 | 0.8 | 29.2 | 0.2 | 2.1 | 2.2 | 7.3 | 7.9 |
| Number of Dedicated Servers | |||||||||||
| None ....................................... | 37.2 | 1.5 | 4.6 | 3.9 | 0.8 | 12.8 | 0.5 | 7.1 | 0.3 | 0.9 | 4.7 |
| 1 to 4 ....................................... | 48.4 | 2.1 | 6.6 | 6.5 | 0.8 | 18.7 | 0.2 | 5.3 | 0.7 | 2.0 | 5.4 |
| 5 to 9 ....................................... | 64.8 | 1.9 | 9.4 | 10.3 | 0.9 | 25.8 | Q | 2.9 | 1.6 | 4.4 | 7.1 |
| 10 to 19 ................................... | 71.4 | 1.8 | 8.3 | 11.7 | 0.7 | 27.5 | 0.2 | 3.9 | 1.6 | 7.6 | 8.3 |
| 20 to 49 ................................... | 70.7 | 1.8 | 12.2 | 9.9 | 0.8 | 27.3 | 0.2 | 2.2 | 2.4 | 5.5 | 8.3 |
| 50 or More .............................. | 79.8 | 2.4 | 7.2 | 8.3 | 0.6 | 33.6 | Q | 2.4 | 7.9 | 7.8 | 9.2 |
| Number of Photocopiers | |||||||||||
| None ....................................... | 39.6 | 1.9 | 4.5 | 3.4 | 1.0 | 12.6 | 0.7 | 9.8 | 0.2 | 0.7 | 4.8 |
| One ......................................... | 38.3 | 1.7 | 4.7 | 4.3 | 0.6 | 14.5 | 0.2 | 6.0 | 0.6 | 1.1 | 4.8 |
| 2 to 4 ....................................... | 46.8 | 1.7 | 6.6 | 6.9 | 0.8 | 17.9 | 0.2 | 3.9 | 1.3 | 2.2 | 5.3 |
| 5 to 9 ....................................... | 58.6 | 2.0 | 8.1 | 9.4 | 0.8 | 22.0 | 0.2 | 2.6 | 1.4 | 5.3 | 6.8 |
| 10 or More .............................. | 72.5 | 2.1 | 10.1 | 10.3 | 0.8 | 30.6 | 0.2 | 2.1 | 2.4 | 5.5 | 8.4 |
| Energy-Related Space Functions | |||||||||||
| (more than one may apply) | |||||||||||
| Commercial Food Preparation.. | 61.9 | 2.3 | 8.7 | 9.1 | 1.3 | 21.9 | 1.0 | 8.3 | 1.0 | 2.5 | 5.9 |
| Activities with Large | |||||||||||
| Amounts of Hot Water ........... | 59.9 | 2.4 | 8.1 | 8.9 | 1.4 | 23.8 | 0.6 | 5.1 | 0.9 | 2.6 | 6.2 |
| Separate Computer Area ........ | 57.7 | 2.0 | 8.1 | 8.6 | 0.9 | 22.9 | 0.2 | 3.2 | 1.7 | 3.8 | 6.3 |
| HVAC Conservation Features | |||||||||||
| (more than one may apply) | |||||||||||
| Variable Air-Volume System... | 64.7 | 2.3 | 9.2 | 9.0 | 0.9 | 25.4 | 0.3 | 3.6 | 1.8 | 4.3 | 7.7 |
| Economizer Cycle ................... | 66.7 | 2.4 | 8.6 | 9.7 | 1.0 | 26.4 | 0.3 | 4.6 | 1.7 | 4.3 | 7.6 |
| HVAC Maintenance ................ | 52.8 | 1.9 | 7.1 | 7.0 | 0.9 | 20.1 | 0.4 | 5.5 | 1.1 | 2.7 | 6.1 |
| Energy Management and | |||||||||||
| Control System (EMCS) ......... | 61.1 | 1.9 | 9.1 | 10.2 | 0.9 | 23.6 | 0.3 | 2.6 | 1.7 | 3.9 | 6.9 |
| Window and Interior Lighting | |||||||||||
| Features (more than one | |||||||||||
| may apply) | |||||||||||
| Multipaned Windows .............. | 52.3 | 2.3 | 6.3 | 6.8 | 0.9 | 20.0 | 0.4 | 5.7 | 1.2 | 2.5 | 6.2 |
| Tinted Window Glass ............. | 56.8 | 1.9 | 7.9 | 7.5 | 0.8 | 22.4 | 0.3 | 4.6 | 1.4 | 3.2 | 6.8 |
| Reflective Window Glass ....... | 61.2 | 2.3 | 9.0 | 8.3 | 0.9 | 24.8 | 0.3 | 3.9 | 1.3 | 3.4 | 7.1 |
| External Overhangs | |||||||||||
| or Awnings ............................ | 55.9 | 2.2 | 7.0 | 7.1 | 1.1 | 19.7 | 0.7 | 8.1 | 1.4 | 2.8 | 5.9 |
| Skylights or Atriums ................ | 51.6 | 1.6 | 6.4 | 7.7 | 0.7 | 21.9 | 0.2 | 2.8 | 1.6 | 2.6 | 6.0 |
| Daylighting Sensors ................ | 71.9 | 2.2 | 10.0 | 10.3 | 0.6 | 27.7 | 0.5 | 4.3 | Q | 4.2 | 8.2 |
| Specular Reflectors ................ | 56.9 | 2.0 | 7.5 | 7.9 | 0.9 | 22.8 | 0.3 | 4.3 | 1.3 | 3.1 | 6.8 |
| Electronic Ballasts .................. | 53.3 | 1.9 | 7.1 | 7.2 | 0.9 | 20.0 | 0.4 | 5.6 | 1.2 | 2.8 | 6.2 |
| Energy Management and | |||||||||||
| Control System (EMCS) | |||||||||||
| For Lighting ............................ | 65.1 | 2.0 | 9.8 | 9.1 | 0.9 | 26.1 | 0.2 | 3.1 | Q | 4.0 | 7.3 |
| Equipment Usage Reduced | |||||||||||
| When Building Not In Full Use | |||||||||||
| (more than one may apply) | |||||||||||
| Heating .................................... | 45.2 | 1.7 | 6.0 | 6.1 | 0.8 | 16.8 | 0.3 | 4.5 | 1.1 | 2.4 | 5.5 |
| Cooling .................................... | 47.0 | 1.7 | 6.5 | 6.4 | 0.8 | 17.5 | 0.3 | 4.6 | 1.0 | 2.6 | 5.6 |
| Lighting ................................... | 42.7 | 1.7 | 5.7 | 5.4 | 0.7 | 14.8 | 0.4 | 5.6 | 0.8 | 2.2 | 5.3 |
| Office Equipment .................... | 37.2 | 1.5 | 5.5 | 5.0 | 0.7 | 13.3 | 0.2 | 4.2 | 0.7 | 1.3 | 4.7 |
| Annual Consumption | |||||||||||
| (kilowatthours) | |||||||||||
| 10,000 or Less ....................... | 4.6 | 0.1 | 0.4 | 0.3 | (*) | 1.5 | (*) | 0.7 | (*) | 0.1 | 1.4 |
| 10,001 to 50,000 ..................... | 16.6 | 0.8 | 2.1 | 1.1 | 0.3 | 5.9 | (*) | 2.4 | 0.4 | 0.5 | 3.1 |
| 50,001 to 100,000 ................... | 27.3 | 1.3 | 3.4 | 2.1 | 0.6 | 8.6 | 0.2 | 5.4 | 0.6 | 0.9 | 4.1 |
| 100,001 to 500,000 ................. | 44.4 | 2.2 | 5.2 | 4.5 | 1.0 | 14.2 | 0.6 | 9.1 | 0.8 | 1.7 | 5.1 |
| 500,001 to 1,000,000 .............. | 49.1 | 2.1 | 7.6 | 6.5 | 1.4 | 17.1 | 0.5 | 6.3 | 0.8 | 1.9 | 5.0 |
| 1,000,001 to 5,000,000 ........... | 69.4 | 2.6 | 9.4 | 10.9 | 1.1 | 26.3 | 0.3 | 5.9 | 1.2 | 4.1 | 7.5 |
| Over 5,000,000 ....................... | 84.1 | 1.8 | 10.9 | 11.4 | 0.8 | 38.8 | 0.3 | 3.2 | 2.4 | 4.9 | 9.6 |
| Provider of Purchased | |||||||||||
| Electricity (more than | |||||||||||
| one may apply) | |||||||||||
| Local Utility .............................. | 46.7 | 1.8 | 6.0 | 5.9 | 0.8 | 17.4 | 0.4 | 5.7 | 0.9 | 2.3 | 5.5 |
| Some Other Provider .............. | 62.3 | 1.8 | 8.9 | 8.5 | 0.6 | 24.6 | 0.2 | 5.1 | Q | 3.3 | 7.1 |
| See "Guide to the Tables" or "Glossary" for
further explanations of the terms used in this table. Both can be accessed
from the CBECS web site - http://www.eia.gov/consumption/commercial/. * Figures in this table do not include enclosed malls and strip malls. In the 1999 CBECS, malls represented 9.7 percent of total electricity consumption. (*)=Value rounds to zero in the units displayed. Q=Data withheld because fewer than 20 buildings were sampled for any cell, or because the Relative Standard Error (RSE) was greater than 50 percent for a cell in the "Total" column. |
|||||||||||
| Notes: ● Due to rounding, data may not sum to totals.
● HVAC = Heating, Ventilation, and Air Conditioning. Source: Energy Information Administration, Office of Energy Markets and End Use, Form EIA-871A, C, and E of the 2003 Commercial Buildings Energy Consumption Survey. |
|||||||||||